IEC 60870-5-103

IEC 60870-5-103 (IEC 103) is the companion standard of IEC 60870-5 for the informative interface of protection equipment. A controlling system (substation controller, bay controller or gateway) polls protection equipment (protection relays) for indications, measurands, settings and fault records. This page explains what matters for using the IEC 103 packages of go-iec60870-5 and iec103ctl.

IEC 103 uses the FT 1.2 frames of IEC 60870-5-1 and the unbalanced link procedures of IEC 60870-5-2, as IEC 101 can, with a one-octet link address, at 9600 or 19200 bit/s on RS-485 or fibre optic. The controlling system starts the link (request status of link, reset of the communication unit or reset of the frame count bit), then polls class 1 while the relay sets ACD (events, answers) and class 2 otherwise (measurands). After a reset the relay identifies itself with ASDU 5. Address 255 is the broadcast, for time synchronization.

IEC 103 does not use the telecontrol ASDU of IEC 101 and 104. Every field of the data unit identifier is one octet, and an information object is addressed by:

  • a function type (FUN): the kind of protection, such as 128 distance, 160 overcurrent, 176 transformer differential, 192 line differential, 254 generic, 255 global;
  • an information number (INF): what the value means for that function type, from tables in the standard (trip, start, protection active, LED reset, auto-reclose and so on), or private.

So a general trip of a distance relay is FUN 128, INF 68 whatever the vendor. The common address of ASDU is normally the link address.

Service ASDUs What it does
Identification 5 The relay’s compatibility level, vendor and software, after a reset or start-up
Time synchronization 6 Addressed, or broadcast to address 255
General interrogation 7, 8 The state of every indication that takes part, ending with the scan number
Events and measurands 1, 2, 3, 4, 9 Time-tagged indications, relative-time events with fault number, measurands as fractions of full scale
General commands 20 Switch protection functions, reset LEDs, as table 17 allows, acknowledged with cause 20 or 21
Generic services 10, 11, 21 Read and write settings and other data by group and entry (GIN), with descriptions, ranges and units
Disturbance data 23 to 31 The list of recorded faults, then one record’s tags and channels, acknowledged part by part
  • Substations with protection relays from several vendors, read by a substation automation system or gateway
  • Retrofits, where IEC 103 relays stay under a newer IEC 61850 or IEC 104 station level
  • Gateways that turn relay events and fault records into IEC 104 or IEC 61850
  • Collecting disturbance records for fault analysis