EtherNet/IP

EtherNet/IP is the industrial Ethernet protocol of programmable controllers, I/O adapters, drives and sensors. It carries the Common Industrial Protocol (CIP) over standard Ethernet, TCP and UDP. ODVA maintains both in The CIP Networks Library: Volume 1 defines CIP and Volume 2 its adaptation to Ethernet. They are also part of the international fieldbus standards IEC 61158 and IEC 61784, as Communication Profile Family 2. This page explains how EtherNet/IP works on the wire, as far as it matters for using go-ethernetip and ethernetipctl.

Role Also called What it is In go-ethernetip In ethernetipctl
Scanner Originator A PLC, a PC application or an edge gateway: it opens connections and sends requests packages client and scanner every command but adapter
Adapter Target An I/O block, a drive, a valve island, a sensor, or a controller answering requests: it holds the objects package server ethernetipctl adapter

A controller is often both. It scans its own I/O adapters, and it is a target for an HMI, a historian or another controller that reads its tags.

Every device listens on TCP port 44818, and on UDP 44818 for discovery. EtherNet/IP wraps each message in a 24-octet encapsulation header: a command, a length, a session handle, a status and a sender context that the reply echoes.

Command What it does
RegisterSession, UnRegisterSession Open and close a session on the TCP connection. Every CIP request travels in a session
ListIdentity Who are you? Vendor, device type, product code, revision, serial number, name and state. Sent over UDP to a broadcast address, it finds every device on a segment
ListServices, ListInterfaces What the device can do: CIP over TCP, I/O over UDP
SendRRData An unconnected request and its reply
SendUnitData A message on a connection

Inside SendRRData and SendUnitData the payload is a common packet format: an address item (null, or a connection ID) and a data item that holds the CIP message.

Objects, classes, instances and attributes

Section titled “Objects, classes, instances and attributes”

Everything a device exposes is an object. A class is a kind of object, an instance is one of them, and attributes are its numbered values. A path such as @1/1/7 names class 1 (Identity), instance 1, attribute 7: the product name.

Class Object What it holds
0x01 Identity Vendor, device type, product code, revision, status, serial number, product name
0x02 Message Router The list of classes the device implements; it dispatches every request
0x04 Assembly Blocks of I/O data: inputs, outputs and configuration
0x06 Connection Manager Opens and closes connections, and counts them
0xF4, 0xF5, 0xF6 Port, TCP/IP Interface, Ethernet Link Ports for routing, IP configuration, link speed and counters

A CIP request is a service on a path: Get_Attribute_Single (0x0E), Set_Attribute_Single (0x10), Get_Attributes_All (0x01), Reset (0x05), Multiple Service Packet (0x0A) to bundle several requests, and services specific to one class. The answer carries a general status, success or a code such as 0x05 (path destination unknown), 0x08 (service not supported) or 0x14 (attribute not supported), and sometimes extended status words that say more.

Device profiles fix which objects a kind of device has, so that drives of different vendors look alike. An Electronic Data Sheet (EDS), a text file from the vendor, describes a device’s identity, parameters, assemblies and connections for configuration tools.

Explicit messages are request and response, for configuration, diagnostics and data that is not time-critical:

  • Unconnected: each request on its own, in SendRRData. Simple, and the way most tools start.
  • Connected: over a Class 3 connection opened with Forward_Open to the Message Router. The device reserves resources for it, and each request carries a sequence count, so a repeated request is detected.
  • Routed: a request for a device behind a gateway, such as a controller in a chassis behind its EtherNet/IP module, goes in an Unconnected_Send with a route path. 1/0 is port 1 (the backplane), slot 0.

I/O data does not wait for requests. A scanner opens a Class 1 connection with Forward_Open (or Large_Forward_Open above 511 octets), naming in its connection path the configuration assembly and two connection points:

Direction What travels Name
O->T (originator to target) The scanner’s outputs, the adapter’s consumed data output assembly
T->O (target to originator) The adapter’s inputs, its produced data input assembly

From then on both ends send a UDP datagram to port 2222 at every RPI (requested packet interval), each with a sequence number so that late and duplicate datagrams are dropped. O->T data usually starts with a 32-bit run/idle header that tells the adapter whether the scanner is in run mode. If datagrams stop for the timeout (a multiple of the RPI), the connection times out and the adapter falls back to its safe state. Forward_Close ends a connection, named by its triad: connection serial number, originator vendor ID and originator serial number.

Connection type What it is
Exclusive owner Writes the outputs. Only one per output assembly
Input only Reads the inputs, with a heartbeat instead of output data. Several may share them
Listen only Like input only, but only while an owner’s connection exists; usually multicast

Inputs can be sent point-to-point to one scanner or by multicast to several, from addresses the device derives from its IP address. Class 0 connections are the same without the sequence count. The Connection Manager refuses a Forward_Open it cannot honour with general status 0x01 and an extended status: 0x0106 (ownership conflict), 0x0127 (wrong O->T size), 0x0119 (listen-only without an owner).

Rockwell Automation’s ControlLogix and CompactLogix controllers add tag services to CIP: Read Tag (0x4C), Write Tag (0x4D), their fragmented forms for large values, Read-Modify-Write for bits, a tag list on the Symbol object and structure definitions on the Template object. These are vendor specific, documented in Rockwell’s Logix 5000 Controllers Data Access manual, and not part of CIP: other devices refuse them. Most open-source “EtherNet/IP libraries” are in fact Logix tag clients.

Transport Port Notes
TCP 44818 Sessions, explicit messages
UDP 44818 ListIdentity and ListServices, including broadcast discovery
UDP 2222 Class 0 and Class 1 I/O
TLS 2221 (TCP) EtherNet/IP over TLS, the CIP Security transport for explicit messaging
DTLS 2221 (UDP) CIP Security for I/O

Plain EtherNet/IP has no authentication: anyone who can reach port 44818 can read and write attributes and open connections that drive outputs, and anyone who can send to port 2222 from a scanner’s address can inject output data. CIP Security (Volume 8) adds TLS and DTLS with certificates or pre-shared keys, configured through its own objects. Keep EtherNet/IP on isolated cell and area networks, and use TLS or a VPN across anything you do not trust.

ODVA sells the specifications as an annual subscription, under its Terms of Usage. A product that implements EtherNet/IP needs an ODVA vendor ID, and passing ODVA’s conformance test earns its Declaration of Conformity; see ODVA in the standards directory. The OT Fabric projects are built from public sources and the behaviour of independent implementations, list every code they use with its source, and make no conformance claim.

Project What it is
go-ethernetip EtherNet/IP and CIP for Go: client, scanner and adapter, Class 0, 1 and 3 connections with multicast and listen-only, Rockwell Logix tags with an emulated controller, EDS files and code generation, EtherNet/IP over TLS. No dependencies outside the standard library. v0.3.1.
ethernetipctl A command-line tool on go-ethernetip: discover, identify, read and write attributes, open connections and stream I/O, diagnose, Logix tags and EDS files; simulate an adapter from a YAML model. v0.2.2.
ethernetip-interop Docker images of twelve independent EtherNet/IP implementations in eight languages behind one container contract, with deterministic fixtures and a cross-stack self-test. v0.4.0.