Testing and interop

Real S7 PLCs differ by family and firmware, and you should never test client code against a running process. OT Fabric tests its S7 client against snap7-interop: two S7 servers built from independent implementations, loaded with the same memory fixtures and checked to behave the same. Since go-s7comm v0.11.0 it is also tested against 25 recordings of real S7-300 and S7-400 CPUs, and snap7-interop publishes OT Fabric’s own S7 server as a third image, so you can test your client against it.

snap7-interop publishes two reference images. Both speak classic S7comm over ISO-on-TCP on container port 102:

Image Implementation
ghcr.io/otfabric/snap7-interop-native Native Snap7, built from the SCADACS fork at a pinned revision (Snap7 1.4.0 lineage, LGPL-3.0-or-later)
ghcr.io/otfabric/snap7-interop-python Pure-Python server from python-snap7 3.2.1, with no native library in the image

The current release is v0.6.1 (container contract 1.1), built for linux/amd64 and linux/arm64. Reference tags never move and there is no latest tag for them; pin by digest where you can. Releases up to v0.2.0 were published as snap-interop-native and snap-interop-python; those tags stay available.

Nothing in the repository outside own/go-s7comm/ depends on go-s7comm, and CI checks it, so any S7 client can use the references. Each run also writes reports/results.json in the organisation’s interop-result-v1 format, one result per fixture.

A fixture is a JSON file that describes the server’s memory: which areas exist, how big they are, whether they are read-only, and their initial contents. It also lists the expected results of reads and writes. A compiler turns typed values into canonical big-endian bytes once, and both servers load the same compiled bytes. Neither server interprets types itself.

{
"$schema": "../schema/fixture.schema.json",
"schemaVersion": "1.0.0",
"id": "basic-db",
"description": "Single zero-filled DB1 with a short hex prefix for smoke reads",
"requires": ["area.db", "operation.read"],
"server": { "rack": 0, "slot": 2, "pduSize": 480 },
"areas": [
{
"type": "db",
"number": 1,
"size": 64,
"access": "read-write",
"initial": { "hex": "0102030405060708" }
}
],
"expectations": [
{
"operation": "read",
"area": { "type": "db", "number": 1 },
"offset": 0,
"length": 8,
"result": { "hex": "0102030405060708" }
}
]
}
  1. Pull an image:

    Terminal window
    docker pull ghcr.io/otfabric/snap7-interop-native:v0.6.1
  2. Start it with a compiled fixture from a checkout of the repository. Map the container’s port 102 to an unprivileged host port such as 1102:

    Terminal window
    docker run --rm -p 1102:102 --read-only \
    --tmpfs /tmp --tmpfs /run/snap-interop:uid=10001,gid=10001,mode=0755 \
    --cap-drop ALL --cap-add NET_BIND_SERVICE \
    -v "$PWD/fixtures/compiled:/fixtures:ro" \
    -e SNAP_INTEROP_FIXTURE=/fixtures/basic-db.compiled.json \
    ghcr.io/otfabric/snap7-interop-native:v0.6.1
  3. Point a client at it, with rack 0 and slot 2:

    Terminal window
    s7commctl read --ip 127.0.0.1 --port 1102 --rack 0 --slot 2 --area DB --db 1 --offset 0 --size 8 --format hex

The container is configured with SNAP_INTEROP_FIXTURE, SNAP_INTEROP_LISTEN_ADDRESS, SNAP_INTEROP_PORT, SNAP_INTEROP_LOG_FORMAT and SNAP_INTEROP_STATE_PATH. It refuses to start with a missing or invalid fixture, logs server_ready once it accepts connections, has a Docker health check, and shuts down cleanly on SIGTERM.

All 15 canonical fixtures pass on both servers:

Fixture What it proves
basic-db Smoke read of DB1
write-cycle An accepted write changes DB1 and is visible on the next read
multiple-dbs Two DBs with distinct contents
markers-io Markers, inputs and outputs
typed-values Typed scalars in a DB and in markers
integer-boundaries Signed and unsigned integer limits, big-endian
floating-point IEEE 754 float32 and float64 patterns
bit-access Single-bit reads and writes inside a DB byte
unaligned-range Multi-byte reads at odd offsets
last-valid-byte A read of the last byte of a DB
out-of-range Out-of-range reads and writes are rejected
read-only-reject A write to a read-only DB is rejected and memory stays unchanged
large-read A large single read within the negotiated PDU
concurrent-reads Several clients read the same bytes at once
reconnect-state Memory survives a client reconnect

Results are normalized to outcomes such as success, address-out-of-range, unsupported, transport-failure and protocol-failure. Each run writes report.json, report.md and junit.xml under reports/<fixture-id>/.

Both reference servers reject a write to a read-only area with item return code 0x0A, not a distinct “write protected” code. The fixture therefore expects address-out-of-range and proves the rejection with a follow-up read. Out-of-range access returns item code 0x05 on both. The Python adapter adds behaviour the stock python-snap7 server lacks (out-of-range rejection, single-bit writes, read-only enforcement) so that both match native Snap7, so agreement on those points is by construction, not two independent observations.

OT Fabric’s own server answers the read-only write with 0x03 (object access not allowed), the code a real CPU 315-2 PN/DP sends for a refused write. snap7-interop v0.6.1 lists this as an intentional, classified difference (tests/known-differences.tsv), with the Siemens documentation as evidence.

Test your client against OT Fabric’s server

Section titled “Test your client against OT Fabric’s server”

ghcr.io/otfabric/snap7-interop-otfabric is the server package of go-s7comm behind the same container contract (adapter name otfabric), so an S7 client can run the same fixtures and commands against it as against the references:

Terminal window
docker run --rm -p 3102:102 --read-only \
--tmpfs /tmp --tmpfs /run/snap-interop:uid=10001,gid=10001,mode=0755 \
--cap-drop ALL --cap-add NET_BIND_SERVICE \
-e SNAP_INTEROP_FIXTURE=/fixtures/basic-db.compiled.json \
ghcr.io/otfabric/snap7-interop-otfabric:latest

Its tags are go-s7comm versions (and latest), not snap7-interop versions, and it is not in a snap7-interop release. It reports independentEngine: false: a result against it is evidence about your client, not independent evidence about go-s7comm. It is test infrastructure only, like the references.

go-s7comm v0.12.0 is qualified against snap7-interop v0.6.1, with the native and Python images pinned by digest. Its build-tagged interop package runs the full fixture matrix against both servers, and all 15 fixtures pass on both:

Terminal window
make interop

This pulls pinned image digests, starts both containers for each fixture on host ports 1102 (native) and 2102 (Python) with rack 0 and slot 2, and runs go test -tags=interop ./interop/.... Variables change what it runs:

Variable Purpose
SNAP_INTEROP_NATIVE_IMAGE, SNAP_INTEROP_PYTHON_IMAGE Use other image references
SNAP_INTEROP_MANAGED=0 Use servers that are already running, at SNAP_INTEROP_NATIVE_ADDR and SNAP_INTEROP_PYTHON_ADDR
SNAP_INTEROP_FIXTURE=<id> Run a single fixture, for example basic-db

make check compiles and lints the interop package but does not start Docker. go-s7comm’s interop workflow runs the full matrix against the pinned images on every push and pull request. A separate, manual Self-interop workflow runs the client against snap7-interop-otfabric; on 2026-11-07 the v0.12.0 client passed all 15 fixtures against the v0.12.0 server image, with the read-only difference above.

testdata/captures holds 25 recordings, made by others, between real CPUs (a CPU 315-2 PN/DP, an IM151-8 PN/DP CPU, an S7-400 and another S7-300) and five clients (Snap7, STEP 7 5.5, TIA Portal V13, WinCC Advanced and libnodave): 14,393 S7 PDUs. They are replayed in the tests, and no live PLC is involved:

  • every PDU decodes, with the counts Wireshark 4.6.9 gives;
  • the requests go-s7comm builds equal, byte for byte, those of Snap7, TIA Portal and libnodave, for setup, Read Var, SZL reads, block functions and uploads;
  • Identify, GetCPUState, GetProtectionLevel, ReadDiagBuffer, BlockCounts, ListBlocks, GetBlockInfo and UploadBlock give, against the recorded answers, the values Snap7 logged or Wireshark decodes;
  • the server answers every recorded Setup Communication, Read Var and Write Var job byte for byte as the CPU did: 26 setups, 3,411 reads (timers, counters and the S7-400’s DBREAD items included) and 2,081 writes.

The recordings showed that, before v0.11.0, the client’s SZL, block and upload requests did not match what real CPUs answer; v0.11.0 fixed them, and the s7commctl commands built on them from v0.5.0.

Besides interop, go-s7comm has unit tests with frame fixtures in testdata/, race detector runs (make test-race), benchmarks for discovery, probing and the wire parsers (make bench), static analysis (make lint, make lint-ci) and govulncheck (make vuln). s7commctl’s own tests cover command wiring, configuration, input validation, output formatting, the write confirmation helpers and the pcap and replay parsers. Protocol codec coverage lives in go-s7comm.

Area Status
DB, marker, input and output byte reads; DB and marker writes Validated on both servers
Single-bit reads and writes Validated
Typed values, boundaries, out-of-range and read-only rejection Validated
Concurrent clients and reconnects Validated
Reads larger than the PDU Chunking happens in the client; the servers cover one large request
Range scans, compare reads, discovery, rack/slot probing Client-side logic, not fixture-tested
Identify, SZL, CPU state, protection level, diagnostic buffer Validated against recorded CPU answers; not in the fixtures, which hold memory only
Block counts, list, info and upload Validated against recorded CPU answers; block download is not covered
Server: timers, counters and DBREAD items Validated against recorded CPU answers; no interop peer has them
Client: timers and counters Tested against go-s7comm’s own fake server only
Optimized S7-1200/1500 data blocks Out of scope
Scan-cycle or program execution Out of scope: the servers hold static memory, not a PLC program