OT Fabric tests its OPC UA implementation against two independent stacks rather than only against itself. opcua-interop packages the reference stacks as Docker images; go-opcua owns the test cases and the published compatibility claims.

Adapter Language Stack version Notes
open62541 C open62541 v1.5.9, OpenSSL crypto backend, mDNS via mdnsd ECC policies, reverse connect, LDS and mDNS
Eclipse Milo Java Eclipse Milo v1.1.8 with milo-encoding-json and milo-encoding-xml No ECC policy, no ReverseHello, not a discovery server

The images are ghcr.io/otfabric/opcua-interop-open62541:<version> and ghcr.io/otfabric/opcua-interop-milo:<version>, for linux/amd64 and linux/arm64. The current release is v0.7.0; tags are immutable. go-opcua pins both images by digest to v0.7.0.

Each image has the same modes: server (start a server from a fixture), client (run one probe operation), test, validate-fixture and print-capabilities.

The reference servers are a safe target for the library and for opcuactl. They build a deterministic address space from a shared fixture, so both stacks expose the same nodes.

  1. Start a server. From a checkout of opcua-interop (needs Docker with BuildKit, make, jq, and openssl 1.1 or later for certificates):

    Terminal window
    make run-open62541 # open62541 server on port 4840
    make run-milo # Milo server on port 4841
  2. Probe it with the reference client.

    Terminal window
    docker run --rm --network host \
    ghcr.io/otfabric/opcua-interop-open62541:latest \
    client read \
    --endpoint opc.tcp://localhost:4840/opcua-interop \
    --node 'nsu=urn:otfabric:opcua-interop:model;s=Scalar.Int32'

    On macOS with Docker Desktop, use --add-host=host.docker.internal:host-gateway and host.docker.internal instead of --network host.

  3. Point your own client at it, for example opcuactl browse tree -e opc.tcp://localhost:4840/opcua-interop --depth 2.

The baseline fixture lives under Objects/Compatibility in namespace urn:otfabric:opcua-interop:model. Always reference nodes by that namespace URI; the index differs between stacks.

Folder Content
Scalars One read/write variable per built-in type, with values chosen to expose encoding errors
Arrays Empty, one-element, multi-element, String, ByteString, 2D matrix
Dynamic Counter (Int64, 250 ms), Toggle (Boolean, 500 ms), Ramp (Double, 100 ms)
Access Read-write, read-only, write-only
Methods Add, Multiply, Echo, NoArguments, MultipleOutputs, Fail
Events Events.Source emits a BaseEvent about every 2 s, Severity 500
History History.Temperature: 5 raw samples
Analog Analog.Level, Analog.Setpoint: AnalogItemType with EURange 0..100, for deadband tests

The fixture user is test-user / test-password. A secured server needs --certificate, --private-key and --pki-dir; the fixture’s securityProfiles decide which secure endpoints are advertised.

Without opcua-interop, the go-opcua repository has runnable servers in examples/server/node_server, map_server, NodeSet2_server and method_server.

Run print-capabilities to see the client operations, client and server features, security profiles and codec support of an image:

Terminal window
docker run --rm ghcr.io/otfabric/opcua-interop-open62541:latest print-capabilities
docker run --rm ghcr.io/otfabric/opcua-interop-milo:latest print-capabilities
Feature (v0.7.0) open62541 Eclipse Milo
DataChangeFilter (absolute and percent deadband, trigger), client and server Yes Yes
Reverse connect Yes No
ECC security policies Yes No
LDS server, mDNS Yes No
Register with an LDS, register-server, find-servers-on-network Yes Yes
codec JSON (OPC UA 1.05) Compact Compact and verbose
codec XML Yes, without DataValue, DiagnosticInfo or matrices Yes

The client mode has eighteen operations, including endpoints, read, write, browse, call, subscribe, event-subscribe, history-read, republish, transfer-subscriptions, node-management and codec. All write JSON to stdout. Client exit codes are 0 success, 2 invalid input, 3 transport or connect failure, 4 OPC UA service failure, 5 fixture validation failure, 6 internal failure and 7 timeout. --channel-lifetime-ms requests a short SecureChannel lifetime to force token renewals during a command.

The suite lives in go-opcua’s interop/ directory behind the interop build tag. Tests start and stop the containers themselves; no pre-running containers or manual steps are needed.

Terminal window
# Test PKI for the security, ECC and secured reverse connect tests
(cd ../opcua-interop && certs/generate.sh)
export OPCUA_INTEROP_PKI_DIR=$PWD/../opcua-interop/certs/test-pki
make interop
# Release verification: fail instead of skip on any missing capability
OPCUA_INTEROP_REQUIRE_CAPABILITIES=1 make interop

The mDNS tests create a user-defined Docker bridge network and cross-compile a go-opcua discovery server into a container, so the daemon must allow bridge networks and Go must be able to build for GOOS=linux with CGO_ENABLED=0. A go-opcua server in a container must be published on the same port it listens on.

Every capability is tested in four directions: Go client to open62541 server (C→O), Go client to Milo server (C→M), open62541 client to Go server (O→S) and Milo client to Go server (M→S). The ledger in interop/COVERAGE.md marks a direction verified only when a named peer test ran against the pinned images without skipping. Go-to-Go tests never earn a verified mark. The README counts 341 verified ledger rows.

Verified in all four directions, among others:

  • Reads of every built-in scalar type, arrays and matrices, batch reads, IndexRange, TimestampsToReturn, write and read-back, access-level rejections.
  • Browse, BrowseNext, ResultMask and filtering, TranslateBrowsePaths, RegisterNodes.
  • Method calls including argument validation and Bad results.
  • Subscriptions: queue size and DiscardOldest windows, timestamps, publishing and monitoring modes, DataChangeFilter absolute and percent deadband, triggers, sampling interval.
  • Security: Basic256Sha256 Sign and SignAndEncrypt, Aes128_Sha256_RsaOaep and Aes256_Sha256_RsaPss SignAndEncrypt, trusted and untrusted certificates, valid and invalid usernames, SecureChannel renewal under a live subscription.
  • Event subscription with OfType and severity filters; raw HistoryRead and continuation points.
  • JSON and XML encodings of Variants.

Verified with open62541 only (C→O and O→S), because Milo 1.1.8 lacks the feature: all five ECC policies including username tokens and renewal (the AEAD policies in SignAndEncrypt only), clean refusal of the brainpool and Curve448 policies, reverse connect including Basic256Sha256, ECC_nistP256 and ECC_nistP384 channels, and mDNS discovery. LDS registration is verified with open62541 in both roles and with Milo registering at a go-opcua LDS; Milo itself is not a discovery server.

  • Deferred: NodeSet2 import, cross-stack custom DataTypes, Query, IssuedIdentityToken, Alarms and Conditions, GDS, custom event emission, the general WhereClause surface for peer clients, HistoryRead modified, at-time, processed and events, HistoryUpdate, certificate chains and CRLs, and secured LDS registration against a peer LDS.
  • Unsupported by a peer: Milo soft-accepts writes with an EncodingMask; the Milo reference server has no NodeManagement; Milo cannot decode a JSON DataValue in the 1.05 inlined form; open62541 1.5.9 has no XML DataValue.
  • ECC Sign mode is tested between two go-opcua instances; against open62541 it was checked once by hand and is not part of the suite.
  • Not certified by the OPC Foundation.
Layer Command What it covers
Unit and race tests make test-norace, make test All packages; coverage gate of 90% on core packages
Integration make integration, make selfintegration Go client against a FreeOpcUa Python server, and against an in-process Go server
Chaos make chaos Faults on unsecured and secured channels (bit flips, replayed, lost and reordered chunks), DataChangeFilter, reverse connect, discovery, codecs; seeds are logged for replay
Fuzzing ua, uasc, uacp fuzz tests Binary, JSON and XML decoders, secure channel, transport

opcuactl v0.3.0 adds end-to-end tests that run the CLI against a go-opcua server. Its published example outputs were captured against a WAGO 750-8102 PFC100 PLC (anonymous and username over None/None only, no events or history) and against a go-opcua v1.6.0 demo server for the ECC, reverse connect, discovery, filter and encoding features.