Testing and interop

OT Fabric tests its IEC 61850 stack against two independent implementations, in both directions: OT Fabric as client against a reference server, and a reference client against the OT Fabric server. This page lists the tools, how to run them, and exactly what the evidence covers.

Simulator What it is Good for
iec61850ctl server start --scl file.icd The go-iec61850 server driven by any ICD, CID or SCD, with optional value seeding from a live device Trying reads, reports and controls against your own model
go-iec61850 NewServer The same server embedded in your Go program, with RegisterControl, SetValue and the report engine Test fixtures in Go code
libiec61850-ied-server (mms-interop) libiec61850 IED server loaded with the interop fixture An independent C reference
iec61850bean-ied-server (mms-interop) IEC61850bean IED server loaded with the interop fixture An independent Java reference
libiec61850-mms-server (mms-interop) Generic MMS server (no IEC 61850 model) Raw MMS with go-mms

Self-tests where an OT Fabric client talks to an OT Fabric server are useful for smoke testing but are not interoperability evidence.

mms-interop owns the adapter images and fixtures, not the assertions. Assertions live in go-mms, go-iec61850 and iec61850ctl.

The current adapter version is 0.1.4 with fixture revision iec61850-v2. Two images are published:

Image Stack Commands
mms-interop-libiec61850 libIEC61850, built from a pinned release archive (GPLv3, runs in its own container, never linked into the Go libraries) libiec61850-mms-server, -mms-client, -ied-server, -ied-client, -ied-controller, -ied-reporter
mms-interop-iec61850bean IEC61850bean 1.x (Apache-2.0), an independent ASN.1/BER, ACSE and MMS implementation iec61850bean-ied-server, -ied-client, -ied-controller, -ied-reporter

IEC61850bean is used only at the IEC 61850 layer; generic MMS interop is covered through libiec61850. Every adapter command supports --capabilities and --version. The authoritative command list is fixtures/capabilities.json in the repository.

The IEC 61850 fixture is fixtures/iec61850/interop.icd plus values.json. It defines the IED InteropIED with the logical device InteropLD. Key objects:

Object Purpose
GGIO1.SPS1.stVal, Mod.stVal The two members of dataset dsInterop
MMXU1.TotW.mag.f MX float read
GGIO1.SPCSO1 / SPCSO2 / SPCSO3 Direct, SBO and SBOw controls
GGIO1.SetInt1.setVal[SP] Writable scalar setting (ING)
urcb01, brcb01 in LLN0 Unbuffered and buffered RCBs

A server adapter prints one readiness line on stdout before accepting connections, then the test connects:

{"event":"ready","address":"0.0.0.0:102","fixture":"iec61850-v1","adapter":"libiec61850","version":"0.1.0"}

Client adapters print one JSON line per operation ({"operation":"read","target":"interop/boolean","ok":true,"value":true}). Diagnostics go to stderr. Fixed-sequence *-ied-client adapters exit 3 when any operation fails and 2 on connection failure.

Terminal window
cd mms-interop
make build
docker run --rm -p 1102:1102 --entrypoint libiec61850-ied-server \
mms-interop-libiec61850:local --port 1102

Then point iec61850ctl at it with IEC61850_IED_NAME=InteropIED:

Terminal window
export IEC61850_HOST=127.0.0.1 IEC61850_PORT=1102 IEC61850_IED_NAME=InteropIED
iec61850ctl list lds --format json
iec61850ctl get object --object InteropLD/MMXU1.TotW.mag.f --fc MX --format json

To drive the OT Fabric server with a reference client, start iec61850ctl server start --host 0.0.0.0 --port 1102 ... on the host and run the adapter with --add-host=host.docker.internal:host-gateway --host host.docker.internal.

The external and reverse suites need Docker. Tests start each adapter with docker run, wait for the readiness line, run, and tear down. Nothing has to be running beforehand.

Terminal window
LIBIEC61850_IMAGE=mms-interop-libiec61850:local make interop

Tests are behind -tags=interop. MMS_SERVER_BINARY and MMS_CLIENT_BINARY skip Docker and use local adapter binaries.

A test skipped without a registered limitation fails CI.

go-mms against libiec61850 (both directions)

Section titled “go-mms against libiec61850 (both directions)”

Associate and conclude, reconnect, Identify, Status, GetNameList, GetVariableAccessAttributes, reads of every fixture type (boolean, integer, unsigned, float32, visible-string, octet-string, bit-string, utc-time, array, structure), single and multi-variable writes, named variable list define, read and delete, and negative cases (unknown domain or variable, wrong type, read-only write).

Not yet tested against a reference: InformationReport, file services and journal services.

go-iec61850 against libiec61850 and IEC61850bean

Section titled “go-iec61850 against libiec61850 and IEC61850bean”
Area Go → libIEC libIEC → Go Go → Bean Bean → Go
Associate, browse LD/LN/DO, ST/MX/CF/DC reads ✓ ✓ ✓ ✓
Write and read-back ✓ ✓ ✓ ✓
Dataset list and read ✓ ✓ ✓ ✓
URCB reserve, enable, data-change report, disable ✓ ✓ ✓ ✓
URCB general interrogation ✓ ✓ ✓ not tested
Direct control ✓ ✓ ✓ ✓
SBO (normal security) ✓ ✓ ✓ ✓
SBOw (enhanced security) ✓ ✓ known gap n/a
Cancel ✓ ✓ not tested not tested
Integrity period not tested not tested not tested not tested
BRCB not in matrix not in matrix not in matrix not in matrix

CDC reads interop-tested: SPS, DPS, INS, ACT, SPC, DPC, MV and BCR. CMV, ENS and BSC are implemented but not interop-tested.

IEC61850bean as a server does not expose SBOw[CO] as a writable attribute, so SBOw from a Go client to IEC61850bean is a registered expected failure. IEC61850bean’s server also does not answer MMS Conclude; tests use Abort.

The CLI suite adds black-box journeys through the binary: browse and reads against expected values, datasets, RCB discovery, URCB GI subscription in JSONL, control operate on SPCSO1/2/3 with --confirm-ref, set object on SetInt1.setVal[SP] with --verify, and BRCB purge and resume by EntryID (required against libiec61850; best effort against IEC61850bean). In the reverse direction, libiec61850 and IEC61850bean controllers, reporters and readers run against iec61850ctl server start. Negative cases cover control mode mismatch, confirmation mismatch and FC=CO rejection.

  • Physical IEDs from any vendor.
  • External BRCB interoperability in the go-iec61850 library matrix (covered by Go-only integration tests and by the CLI against libiec61850).
  • Integrity-period reporting against a reference stack.
  • Edition 2.1 (2007B4) features beyond those listed.
  • Dynamic dataset creation on the server, CommandTermination and TimeActivatedOperate (not implemented).
  • File and journal services in reverse (reference client to OT Fabric server).
  • Adapter fault injection such as mid-sequence disconnects.