Siemens S7

S7comm is the Siemens application protocol that engineering tools, HMIs (human-machine interfaces) and other controllers use to talk to classic SIMATIC S7 programmable logic controllers (PLCs). It runs over Ethernet as ISO-on-TCP: a stack of three thin transport layers on TCP port 102, with S7comm on top.

┌──────────────────────────────────────────────┐
│ S7comm setup communication, read/write │
│ variables, SZL, blocks, diagnostics│
├──────────────────────────────────────────────┤
│ COTP ISO 8073 Class 0 transport: │
│ connect request/confirm, TSAPs, │
│ data TPDUs │
├──────────────────────────────────────────────┤
│ TPKT RFC 1006 framing: version + │
│ length header around each TPDU │
└──────────────────────────────────────────────┘
TCP port 102

This page covers the classic S7comm protocol. It does not cover the newer S7comm-plus protocol, or the optimized data blocks of S7-1200 and S7-1500 controllers.

TPKT (RFC 1006) lets ISO transport traffic run over a TCP byte stream. Each packet has a four-octet header (version 3, a reserved octet, and a 16-bit length) followed by one transport protocol data unit (TPDU). A valid packet is between 7 and 65535 octets long. If TPKT framing breaks, the session ends before any S7 work happens. Tool messages like read TPKT header: EOF usually mean the peer closed the connection during the handshake.

COTP (connection-oriented transport protocol, ISO 8073 / X.224) runs in Class 0 (TP0) for S7. The client sends a connection request (CR) TPDU and the server answers with a connection confirm (CC). The CR carries two TSAPs (transport service access points), a local and a remote one, and both sides agree on a maximum TPDU size. After that, S7 messages travel in data (DT) TPDUs. A message larger than one TPDU is split into segments and reassembled on the other side. The complete reassembled unit is a TSDU (transport service data unit).

S7comm starts with Setup Communication. The client offers a maximum PDU size and the number of parallel jobs it wants to run (AMQ, “max AMQ calling” and “max AMQ called”). The PLC answers with the values it accepts. Only then can the client send real jobs.

Siemens hardware is addressed by rack (a chassis, 0 to 7) and slot (a module position in that rack, 0 to 31). An S7-300 CPU usually sits in rack 0, slot 2. Other families and many soft PLCs use slot 0 or slot 1.

The remote TSAP is where rack and slot end up on the wire. It is a 16-bit value: the high byte is the connection type (1 for PG, the programming device; 2 for OP, an operator panel; 3 for S7 basic communication), and the low byte packs rack and slot. Pick the wrong rack or slot and the PLC refuses the COTP connection or the setup.

In practice, endpoints differ:

  • Some accept exactly one rack/slot pair.
  • Some accept many pairs and behave the same for all of them.
  • Gateways, protocol converters and simulators may accept setup for any pair, but not map it to a real CPU.

So a successful setup is weaker evidence than a successful follow-up query. The OT Fabric tools keep the two apart: setup accepted means TCP, COTP and Setup Communication worked; query confirmed means a harmless read-only query (a system status list read or a CPU state request) also worked.

The negotiated PDU size is the largest S7 message, in bytes, that either side will send. Typical values are 240, 480 and 960. It limits how much data one read or write can carry, so a client splits larger requests into several jobs. A negotiated PDU size proves setup worked. It does not prove that every service is available.

S7comm is request and response. The header field ROSCTR (remote operating service control) gives the message kind:

ROSCTR Name Meaning
1 Job Request from the client
2 Ack Acknowledgement without data
3 Ack-Data Acknowledgement carrying data
7 Userdata Extended services such as SZL reads and block lists

Each request carries a PDU reference that the response echoes back. An Ack can carry an error class and error code in its header. A Read Var response also has a return code per item: 0xFF means success, and codes such as 0x05 (address out of range) or 0x0A (object not available) mean that one item was refused, even when the job as a whole succeeded.

S7 variable access is organized into areas:

Area Letter Contents
Data blocks DB Structured program data. Each DB has a number, for example DB1. Usually the most useful area.
Inputs I (German: E) The process image of field inputs
Outputs Q (German: A) The process image of outputs the PLC drives
Markers M (also called merkers or flags) Internal memory used by the PLC program
Timers T Timer values
Counters C (German: Z) Counter values

An address names an area, a DB number for data blocks, a byte offset and a size. Bits are addressed as byte and bit: DB1.DBX10.3 is bit 3 of byte 10 in DB1. Bytes, words and double words are DBB, DBW and DBD. Multi-byte values are big-endian. A REAL is an IEEE 754 32-bit float. An S7 STRING has two header bytes (maximum length and current length) before the characters.

Do not assume that an area is a flat block of memory. A PLC may expose only part of an area, return fewer bytes than asked for, or refuse some addresses. That is why OT Fabric reports a read as success, short-read, empty-read or rejected instead of a single success or failure.

The SZL (System-Zustands-Liste, system status list) is how a CPU describes itself. Each list has an ID and an index. Commonly read lists include the module identification (order number and firmware version), component identification (module name, serial number, plant ID), the CPU state (RUN, STOP, STARTUP or HOLD), the protection level and the diagnostic buffer (ID 0x00A0).

Not every device fills every field. Missing values do not mean the device is not a Siemens PLC. They may only mean that this model or firmware does not expose them.

A PLC program is made of blocks:

Block Meaning
OB Organization block, called by the operating system (for example the main cycle, OB1)
FB Function block, with its own instance data
FC Function, without persistent data
DB Data block
SFB / SFC System function blocks and system functions built into the CPU firmware

Clients can list blocks, read a block’s metadata (language, size, timestamps) and upload a block, which copies it from the PLC to the client. Whether this works depends on the CPU family, the protection level and the access rights of the connection.

Classic S7comm has no authentication and no encryption. Any host that can reach TCP port 102 and knows a valid rack and slot can read memory and, unless the CPU’s protection level blocks it, write memory. Protection levels set in the hardware configuration can restrict writes and block access, but they are not a replacement for network controls.

S7-300, S7-400, S7-1200 and S7-1500 controllers run machines, production lines and utility processes in manufacturing, water treatment, building services and energy. In energy systems they often control balance-of-plant equipment such as pumps, cooling, switchgear interlocks and combined heat and power units, and they sit next to the protocols that face the grid.

Source code: go-s7comm, s7commctl, snap7-interop, go-cotp, go-tpkt. Read on in the Go library, s7commctl and testing and interop pages.