Testing and interop
IEC 60870-5-104 implementations disagree in small ways: a missing type, a refusal without the P/N bit, a timer that cannot be switched off. OT Fabric tests its IEC 104 code in three layers: tests inside each repository, a simulated station for hardware-free work, and an interop suite that runs the library against five independent stacks on every push, one of them with the application-layer security of IEC 62351-5.
Simulators
Section titled “Simulators”You have two stations to test against without hardware:
| Simulator | Where | Use it for |
|---|---|---|
iec104ctl server start |
iec104ctl | Developing a SCADA front end or gateway. A YAML model with simulated values, select-before-operate, queued events, redundant connections, files, TLS and IEC 62351-5 with roles |
go run ./iec104/examples/server -addr :2404 |
go-iec60870-5 | A small station with single and double points, measurements, counters, a commandable switch and spontaneous updates |
| Reference servers in containers | iec60870-5-interop | Checking your code against lib60870-C, j60870, wendy512/iec104, cB-Sigma/iec60870 or part5 |
# A simulated station for a CI pipeline, stopped after 60 secondsiec104ctl server start --config model.yaml --duration 60Tests inside the repositories
Section titled “Tests inside the repositories”go-iec60870-5 needs no hardware and no external process:
make check # format, lint, vet, vulnerability scan, tests with -race, coverage floors, examples, docsmake fuzz # fuzz targetsmake interop # IEC 104 against the pinned reference images (Docker)| Layer | How it is tested |
|---|---|
iec104/apci, asdu |
Byte vectors from the standard, round trips over every type identification, error tables, fuzzing |
iec104/internal/link |
A scripted peer writing raw APDUs over loopback TCP: windows, each timer, each violation |
iec104/client, iec104/server |
Against each other over loopback TCP, including TLS, reconnect and server restart |
sec |
Encodings checked against octet strings from cB-Sigma/iec60870’s encoder and RFC 3394 and RFC 5869 vectors; two endpoints on a simulated connection through every procedure, timeout, failure and backoff; tampered and replayed messages, refused certificates and algorithms; fuzzing |
iec104/e2e |
Client against server end to end over TCP, TLS, with k = w = 1 and with IEC 62351-5; a wire matrix of all 67 type identifications in every variant; 40,000 frames each way to wrap the 15-bit sequence numbers |
| Recorded traffic | Public IEC 104 captures replayed through the decoders, client and server, and checked against Wireshark’s dissector |
iec104ctl runs every command through the real command tree against an in-process simulated station, over TCP and TLS, in all three output formats, with its exit codes, and against go-iec60870-5’s own servers and clients (make e2e in iec60870ctl).
The interop suite
Section titled “The interop suite”iec60870-5-interop v0.5.0 (container contract 2.3) packages independent implementations of the whole IEC 60870-5 family as container images. For IEC 104 there are five, each with client and server:
| Adapter | Implementation | Language | Image |
|---|---|---|---|
lib60870 |
MZ Automation lib60870-C v2.4.1 | C | ghcr.io/otfabric/iec60870-5-interop-iec104-lib60870 |
openmuc |
OpenMUC j60870 1.8.0 | Java | ghcr.io/otfabric/iec60870-5-interop-iec104-openmuc |
wendy512 |
wendy512/iec104 v1.0.4 on go-iecp5 v1.2.6 | Go | ghcr.io/otfabric/iec60870-5-interop-iec104-wendy512 |
cbsigma |
cB-Sigma/iec60870 v0.3.0 | Go | ghcr.io/otfabric/iec60870-5-interop-iec104-cbsigma |
part5 |
pascaldekloe/part5 v0.3.0 | Go | ghcr.io/otfabric/iec60870-5-interop-iec104-part5 |
cB-Sigma/iec60870 is the only one with IEC 62351-5. The contract covers interrogation groups, a quality on M_BO_NA_1, mutual TLS (IEC 62351-3), file transfer and the file directory, and redundancy groups (edition 2, clause 10), each behind a feature in print-capabilities. The suite follows the latest upstream release even when it has a bug: j60870 1.8.0 cannot decode a read command (C_RD_NA_1) and closes the connection on one, so the read cases of j60870 pairings are listed as a known upstream bug, and the self-test fails once a release fixes it (fix proposed upstream). The images run as a non-root user, with base images pinned by digest and upstream sources by commit or exact version.
The repository owns the adapters, a fixture format and a baseline fixture per standard. Every server adapter serves the fixture the same way. It does not contain any library under test; go-iec60870-5 and iec60870ctl pull the images and own their own scenarios and assertions.
Running it
Section titled “Running it”Needs Docker and jq.
-
Build the images and check the container contract:
Terminal window make images # build every adapter image for this machinemake smoke-iec104 # container contract of each IEC 104 imagemake interop-iec104 # every IEC 104 client against every IEC 104 server -
Run a reference server and wait until it is ready:
Terminal window docker run -d --name ref -p 127.0.0.1:2404:2404 \ghcr.io/otfabric/iec60870-5-interop-iec104-lib60870:v0.5.0 serveruntil docker exec ref test -f /run/iec60870-5-interop/ready; do sleep 0.1; done -
Run a reference client of another stack against it:
Terminal window docker run --rm --add-host=host.docker.internal:host-gateway \ghcr.io/otfabric/iec60870-5-interop-iec104-openmuc:v0.5.0 \client interrogate --host host.docker.internal --port 2404 | jq .
Every image has the same commands: server, client <operation> (connect, interrogate, counter-interrogate, read, clock-sync, test-command, command, monitor, file-get and more), print-capabilities and print-fixture. A client prints one JSON result document; a server prints a JSON Lines stream of what it received. Wait for the readiness file, never for a delay. Pin images by digest for release qualification; the digests are in each release’s manifest.json.
Capabilities
Section titled “Capabilities”The stacks do not all support the same. Each image declares what it supports with print-capabilities, and test suites skip, rather than fail, what an image lacks.
| lib60870 | openmuc | wendy512 | cbsigma | part5 | |
|---|---|---|---|---|---|
| General, group and counter interrogation, read, clock sync, test command | yes | yes ¹ | yes | yes | yes |
| Direct commands, select-before-operate, deactivation | yes | yes | yes | yes | yes |
| Commands with time tag | yes | yes | no | yes | yes |
| File transfer and directory | yes | yes | partly | yes | no |
| Redundancy groups: station / controlling station | yes / yes | yes / yes | no / yes | yes / yes | no / no |
| TLS: station / controlling station | yes / yes | yes / yes | no / yes | yes / yes | no / no |
| IEC 62351-5 | no | no | no | yes | no |
¹ Read is declared, but j60870 1.8.0 closes the connection on a read command; those cases count as a known bug.
The gaps of wendy512 are those of go-iecp5 v1.2.6, and part5 v0.3.0 has no TLS, file transfer or redundancy; the evidence is in CAPABILITIES.md.
Test your stack against OT Fabric’s
Section titled “Test your stack against OT Fabric’s”ghcr.io/otfabric/iec60870-5-interop-iec104-otfabric is go-iec60870-5 behind the same container contract as the reference images (adapter name otfabric), new with iec60870-5-interop v0.5.0, so you can test your IEC 104 controlling station or controlled station against it, the way OT Fabric tests its own stack against yours:
docker run -d --name go-iec104 -p 127.0.0.1:2404:2404 \ ghcr.io/otfabric/iec60870-5-interop-iec104-otfabric:<tag> serveruntil docker exec go-iec104 test -f /run/iec60870-5-interop/ready; do sleep 0.1; doneThe station serves the baseline fixture on port 2404, with TLS, IEC 62351-5, files and redundancy groups behind their flags, and client <operation> runs go-iec60870-5’s controlling station against yours. One difference from the references: go-iec60870-5 takes w independently of k, but the image keeps the contract’s rule w <= k.
Its tags are go-iec60870-5 versions, such as v0.5.1, and latest; a rebuild of a version replaces its tag, so pin the digest when you need an exact build, and version prints the versions inside the image. It is not part of an iec60870-5-interop release or its manifest.json, and it reports independentEngine: false: a result against it tells you about your stack, not something independent about OT Fabric’s. A result you publish, naming your implementation and version, is independent evidence. Like the references, it is for testing only and has no place on a network you do not control.
What go-iec60870-5 is validated against
Section titled “What go-iec60870-5 is validated against”go-iec60870-5 v0.5.1 runs its IEC 104 client and server against the five IEC 104 images of iec60870-5-interop v0.4.0, pinned by digest, on every push and pull request (make interop). The last recorded run (2026-11-12): 519 subtests passed, 35 skipped, none failed.
| Reference | Client to reference server | Reference client to server |
|---|---|---|
| lib60870-C v2.4.1 | pass | pass |
| j60870 1.8.0 | pass, without file download and read | pass, without read |
| wendy512/iec104 v1.0.4 on go-iecp5 v1.2.6 | pass, without time-tagged commands and file transfer | pass, without time-tagged commands and file transfer |
| cB-Sigma/iec60870 v0.3.0 | pass, and IEC 62351-5 | pass, and IEC 62351-5 |
| pascaldekloe/part5 v0.3.0 | pass, without file transfer, TLS and redundancy | pass, without file transfer, TLS and redundancy |
As client it is checked for: interrogation, counter interrogation and read value by value against the fixture; every command type with and without time tag, select-before-operate and deactivation; the refusals (unknown type, cause, common address, object); STARTDT/STOPDT cycles; k = w = 1; the idle test in both directions; reconnect after a station restart; concurrent sessions; file transfer; and a redundancy group across two stacks with failover and switchover.
As server each reference client’s complete result (every ASDU, in order, field by field) must equal what the same client gets from the reference server of its own stack.
IEC 62351-5 is tested against cB-Sigma/iec60870 in two ways. In the container suite, go-iec60870-5’s client associates with the cB-Sigma station and the cB-Sigma client with a go-iec60870-5 station: certificates from an authority and pinned, secp256r1 and X25519, HMAC-SHA-256 and AES-256-GCM, other association identities, a viewer’s command refused with cause 17 and an operator’s executed, an AIM the station refuses, untrusted certificates on either side and a client without security. In process (iec104/interop/cbsigma, a module of its own so the library keeps no dependencies), the encodings of every message are compared and complete associations run in both roles.
To test against another build, set IEC104_INTEROP_LIB60870_IMAGE, IEC104_INTEROP_OPENMUC_IMAGE, IEC104_INTEROP_WENDY512_IMAGE, IEC104_INTEROP_CBSIGMA_IMAGE or IEC104_INTEROP_PART5_IMAGE; to run one stack only, IEC104_INTEROP_ADAPTERS=lib60870.
iec104ctl v0.9.1 runs against the same five references in both roles: 42 checks pass, and the read against j60870 1.8.0 is the known upstream bug.
What has not been validated
Section titled “What has not been validated”- Certified test equipment and field devices. None of the projects has been run against them. Interoperability reports are welcome, with the
--debugtrace for iec104ctl. - TLS with wendy512 and part5. go-iecp5 has no TLS station and part5 no TLS at all; TLS is tested against lib60870-C, j60870 and cB-Sigma.
- IEC 62351-5 beyond cB-Sigma. The security code was derived from cB-Sigma/iec60870, not from the IEC documents, and no third implementation or certified test equipment has checked either. Treat it as interoperable with cB-Sigma, not as conformance-tested. iec104ctl’s
--secureis tested against its own simulated station and relies on the library’s tests against cB-Sigma. - Edges of file transfer and redundancy. The suite does not compare NOS of
F_AF_NA_1with AFQ 1 and 2,sequenceandtimeInvalidofF_DR_TA_1, or whether a connection that was taken over is closed. - Type identifications outside the fixture. The interop suite covers
M_SP,M_DP,M_ST,M_BO,M_ME_NA/NB/NC,M_ITand their CP56Time2a variants, the six command types, and the system commands. Everything else (protection events, packed points, bitstring commands, parameters) is covered by codec tests only. - Edition 2 and Amendment 1. The library follows edition 1 (2000); where the code follows edition 2 behaviour that edition 1 does not describe, it is marked as such in the library’s IEC 104 interoperability list.
- Faults. The references are correct peers, not fault injectors. Malformed frames, wrong sequence numbers and timer boundaries are tested with the library’s scripted peers.