IEC 60870-5-102
IEC 60870-5-102 (IEC 102) is the companion standard of IEC 60870-5 for the transmission of integrated totals in electric power systems: reading the energy counters of electricity meters, period by period. A controlling station (a metering front end or data collector) reads an integrated total station (a meter or data concentrator) over a serial line, a modem or a terminal server. This page explains what matters for using the IEC 102 packages of go-iec60870-5 and iec102ctl.
Link and frames
Section titled “Link and frames”IEC 102 uses the FT 1.2 frames of IEC 60870-5-1 and the unbalanced link procedures of IEC 60870-5-2, like IEC 101: the controlling station starts the link (request status of link, reset of remote link), sends a request with send/confirm, and polls class 2 data until the answer is complete. IEC 102 has no spontaneous data: a meter only answers what it is asked, so there is nothing to monitor between requests. Link address and common address are usually two octets.
Records, totals and periods
Section titled “Records, totals and periods”IEC 102 has an application layer of its own, not the telecontrol ASDU of IEC 101 and 104. After the data unit identifier comes a record address, then the information objects; a list of integrated totals ends with one common time tag.
| Record address | Holds (as REE meters use them) |
|---|---|
| 11, 12 | Integration periods 1 and 2: the hourly (or quarter-hourly) load profile |
| 21 | Daily values |
| 1 | The accounting (billing) period |
| 50 to 55 | Lists of single-point events |
A request names a record, a range of integrated total addresses (in the REE profile: 1 active import, 2 active export, 3 to 6 the reactive quadrants) and a time window. The meter confirms the request (cause 7), sends one ASDU per integration period (cause 5) and terminates it (cause 10), or refuses it with a cause of refusal (13 to 18: no record, unknown type, unknown record number, unknown record address, no object, no period). Each total has a quality octet: overflow, adjusted, invalid.
Time a and time b
Section titled “Time a and time b”IEC 102 has its own time formats, not the time tags of IEC 60870-5-4. Time a (minute to year, with tariff flags and the summer time bit SU) stamps the end of an integration period; time b adds seconds and milliseconds for the meter’s clock. Meters keep local time, and the SU bit tells the repeated hour at the end of summer time apart.
The Spanish REE profile
Section titled “The Spanish REE profile”Spanish fiscal metering, run by Red Eléctrica (REE), uses IEC 102 with additions in the private range of type identifications: a session opened with an access key (C_AC_NA_2) and closed again (C_FS_NA_2), clock setting, tariff information of the contracts, contracted powers and special days, and other meanings for some quality bits. None of it is IEC 102 itself. go-iec60870-5 keeps it in a separate package and applies it only when asked.
Where it is used
Section titled “Where it is used”- Spanish fiscal metering of generation, transmission and large consumers
- Energy meters and data concentrators in substations and power plants
- Meter data collection for billing and settlement
OT Fabric for IEC 60870-5-102
Section titled “OT Fabric for IEC 60870-5-102”Source code: go-iec60870-5, iec60870ctl, iec60870-5-interop.