IEC 60870-5-101

IEC 60870-5-101 (IEC 101) is the serial telecontrol companion standard of IEC 60870-5: a control centre (the controlling station) exchanges process data with RTUs (the controlled stations) over serial lines, leased lines, modems and radio. Its application messages are the ones IEC 104 carries over TCP; underneath, it has the frames and link procedures of IEC 60870-5-1 and -2. This page explains what matters for using the IEC 101 packages of go-iec60870-5 and iec101ctl.

IEC 101 uses the FT 1.2 frame format of IEC 60870-5-1, at 8 data bits, even parity and one stop bit:

Frame Layout Used for
Single character E5 A short acknowledgement, or “no data”
Fixed length 10 control, address, checksum, 16 Link services without user data: status, reset, polls
Variable length 68 L L 68 control, address, ASDU, checksum, 16 User data: one ASDU per frame

The checksum and the doubled length make a broken frame easy to detect, and the receiver resynchronizes on the next start character.

IEC 60870-5-2 defines how the two ends use those frames. IEC 101 allows two modes:

  • Unbalanced. The controlling station is the only primary station. It brings up each station’s link (request status of link, reset of remote link), sends commands with send/confirm, and polls for data: class 1 (events, answers) while the station sets the ACD bit, class 2 (cyclic data) otherwise. Because only the master speaks first, many stations can share one line (multidrop), each with its own link address.
  • Balanced. Both ends are primary and send when they have something, on a full-duplex point-to-point line. Each direction is initialized on its own.

The frame count bit (FCB, with FCV) lets a station recognize a repeated frame, so a command that was answered but whose answer was lost is not executed twice. The DFC bit tells the primary that the station’s buffer is full.

Where IEC 104 fixes its field sizes, IEC 101 leaves them to the project:

Field Octets Common
Link address 0 (balanced only), 1 or 2 1
Cause of transmission 1, or 2 with the originator address 1
Common address of ASDU 1 or 2 1
Information object address 1, 2 or 3 2

Nothing on the wire says which sizes a station uses. A wrong setting shows as scrambled addresses or a station that ignores every request, so check the station’s interoperability list first.

The ASDU is the telecontrol ASDU of the family: a type identification, a variable structure qualifier, a cause of transmission, the common address of the station and one or more information objects, each with its information object address. The services are those of IEC 104:

  • General and group interrogation (C_IC_NA_1) for the state of every point; counter interrogation (C_CI_NA_1) for integrated totals; read (C_RD_NA_1) of one address.
  • Spontaneous events with CP24Time2a or CP56Time2a time tags, and cyclic measured values.
  • Commands (single, double, regulating step, set points, bitstrings), direct or select-before-operate, with confirmation and termination.
  • Clock synchronization (C_CS_NA_1), the test command (C_TS_NA_1, without time tag in IEC 101), reset process (C_RP_NA_1) and delay acquisition (C_CD_NA_1), which measures the transmission delay of a slow line so that the station can correct the time it was given.

A 101 network often sits behind a gateway that speaks IEC 104 to the control centre, or behind a terminal server that carries the serial byte stream over TCP unchanged. Over such a TCP connection it is still IEC 101: FT 1.2 frames and link procedures, not the APCI of IEC 104. iec101ctl and the interop images talk to a terminal server on TCP port 2401 by default.

  • Distribution and older transmission networks with RTUs on serial, radio or leased lines
  • Multidrop lines and radio networks polled from one control centre port
  • Pipelines, water and district heating SCADA
  • Behind 101-to-104 gateways and terminal servers

Source code: go-iec60870-5, iec60870ctl, iec60870-5-interop.