IEC 60870-5-104

IEC 60870-5-104 (IEC 104) is the TCP/IP telecontrol protocol between control centres and substations, remote terminal units (RTUs) and generation assets. It carries the application messages of its serial sibling IEC 60870-5-101 over TCP, by default on port 2404.

Two roles take part in every connection:

  • The controlling station (the control centre or a SCADA front end) is the TCP client.
  • The controlled station (an RTU, a substation gateway or an intelligent electronic device, IED) is the TCP server.

The standard has two layers. The APCI (application protocol control information) runs the TCP connection: framing, sequence numbers, acknowledgements and link supervision. The ASDU (application service data unit) is the payload: what kind of data, why it was sent, for which station and which point.

┌──────────────────────────────────────────────┐
│ ASDU type identification, cause of │
│ transmission, common address, │
│ information objects │
├──────────────────────────────────────────────┤
│ APCI APDU framing, I/S/U frames, │
│ sequence numbers, acknowledgements, │
│ STARTDT / STOPDT / TESTFR │
└──────────────────────────────────────────────┘
TCP (optionally TLS)

Every APDU (application protocol data unit) starts with the octet 0x68 and a length. A whole frame is at most 255 octets, the APDU after the start and length octets at most 253, and the ASDU inside at most 249. There are three frame formats:

Format Carries Purpose
I (information) An ASDU, a send sequence number N(S) and a receive sequence number N(R) Application data in either direction
S (supervisory) N(R) only Acknowledges received I frames when there is nothing to send
U (unnumbered) One function STARTDT, STOPDT and TESTFR, each as activation (act) and confirmation (con)

Sequence numbers are 15 bits wide and wrap at 32768. Every I frame a side sends counts up N(S); the N(R) it sends back acknowledges every I frame received up to that number. An I frame of your own also acknowledges, so an S frame is only needed when one side is quiet.

A fresh TCP connection carries no application data. The controlling station sends STARTDT act and the station answers STARTDT con; only then do I frames flow. STOPDT stops data transfer without closing the connection. This is what makes redundancy work: a station can hold several connections open and send its events on the one that is started.

Parameter Default Meaning
k 12 Maximum number of I frames sent and not yet acknowledged. A sender stops at k
w 8 Acknowledge at the latest after this many received I frames
Timer Default Meaning
t0 30 s Connection establishment timeout (client)
t1 15 s Timeout for the acknowledgement of a sent I frame or the confirmation of a U frame. Expiry closes the connection
t2 10 s Longest wait before acknowledging received I frames when there is nothing to send. Must be below t1
t3 20 s Idle time before a TESTFR act is sent to check that the link is alive

The parameters are not negotiated. Both ends must be configured alike, and you change them only to match a station that deviates.

An ASDU has a header and one or more information objects. With the IEC 104 field sizes the header is:

Field Size Meaning
Type identification 1 octet What kind of object the ASDU carries
Variable structure qualifier 1 octet Number of objects (up to 127) and the SQ bit
Cause of transmission 2 octets Why the ASDU was sent, the P/N (positive/negative) and T (test) bits, and the originator address
Common address of ASDU 2 octets The station
Information object address 3 octets per object The point

Here is a real read request from an iec104ctl debug trace, decoded:

I N(S)=0 N(R)=0 len=9 C_RD_NA_1 request ca=1 n=1 [66 01 05 00 01 00 64 00 00]
66 type identification 102 (C_RD_NA_1, read command)
01 one object, SQ = 0
05 00 cause 5 (request), originator 0
01 00 common address 1
64 00 00 information object address 100

With SQ = 0 each object carries its own address. With SQ = 1 one address is followed by consecutive elements, a compact form for a run of adjacent points.

  • The common address (CA) names a station. A gateway can answer for several stations behind one connection. Address 65535 is the broadcast address.
  • The information object address (IOA) names one point within a station: a breaker position, a voltage, a command. With three octets it ranges from 1 to 16,777,215.

There are no names on the wire. A station does not tell you that IOA 1000 is “Voltage L1”; the station’s signal list is where addresses get their meaning.

The type name encodes direction and time tag. M_ types travel in monitor direction (station to centre), C_ in control direction, P_ are parameters and F_ file transfer. A suffix such as _TB_1 marks a variant with a time tag.

Range Group Examples
1..40 Process information, monitor direction M_SP_NA_1 (1) single point, M_DP_NA_1 (3) double point, M_ME_NC_1 (13) short floating point measured value, M_IT_NA_1 (15) integrated totals, M_SP_TB_1 (30) single point with CP56Time2a
45..64 Process information, control direction C_SC_NA_1 (45) single command, C_DC_NA_1 (46) double command, C_SE_NC_1 (50) floating point set point, C_SC_TA_1 (58) single command with CP56Time2a
70 System information, monitor direction M_EI_NA_1 end of initialization
100..107 System information, control direction C_IC_NA_1 (100) interrogation, C_CI_NA_1 (101) counter interrogation, C_RD_NA_1 (102) read, C_CS_NA_1 (103) clock synchronization, C_TS_TA_1 (107) test command
110..113 Parameters P_ME_NC_1 (112), P_AC_NA_1 (113) parameter activation
120..127 File transfer F_FR_NA_1 (120) file ready, F_SG_NA_1 (125) segment, F_DR_TA_1 (126) directory
128..255 Private range Vendor specific

CP56Time2a is the seven-octet time tag (date and time to the millisecond); CP24Time2a carries only minutes, seconds and milliseconds. The CP24Time2a types (2, 4, 6 and so on) belong to IEC 60870-5-101 and are not part of the IEC 104 subset. A time tag carries no time zone: both ends have to agree on one.

Values carry a quality descriptor with the flags IV (invalid), NT (not topical), SB (substituted), BL (blocked) and OV (overflow).

The cause of transmission (COT) says why an ASDU was sent. The ones you meet daily:

Cause Meaning
3 spontaneous A change the station reports on its own
periodic, background Cyclic data
5 request Answer to a read command
6 activation, 7 activation confirmation A command or request and its confirmation
8 deactivation, 9 deactivation confirmation Cancelling a command, for example a selection
activation termination The end of a procedure (an interrogation, an executed command)
11 return information, remote command The state change caused by a command
13 file transfer File transfer ASDUs
20 interrogated by station, 21..36 groups 1..16 Answers to a general or group interrogation
37 requested by general counter request Answers to a counter interrogation
44..47 Unknown type identification, cause, common address or information object address

A station refuses a request by mirroring it with the P/N bit set, or with one of the causes 44..47.

  • General interrogation (C_IC_NA_1, qualifier QOI 20) makes a station send its whole process image: activation confirmation, the data with cause 20, activation termination. Groups 1..16 use QOI 21..36. Integrated totals are not included; a counter interrogation (C_CI_NA_1) reads them, optionally with freeze or reset.
  • Spontaneous reporting: after the interrogation the station sends changes as they happen, usually with a CP56Time2a time tag.
  • Clock synchronization (C_CS_NA_1) sets the station’s clock, and with it the time tags of its events.
  • Commands are confirmed (cause 7) and, when carried out, terminated. The effect arrives as a separate monitor-direction event, usually with cause 11.

A command can be sent in two steps. The select (S/E bit = 1) asks the station to confirm that the object is free and the command acceptable. The execute (S/E = 0) then carries it out. A selection can be cancelled with a deactivation (cause 8). Stations can require a select before an execute; they keep the selection per connection, so a select and its execute must use the same connection.

The standard lets a controlled station serve several connections of one redundancy group, of which exactly one is started. The control centre keeps the others established in STOPDT and supervised by test frames. On failover it sends STARTDT on a standby, and the station moves its event stream there. Events the old connection had not acknowledged are sent again on the new one, so the control centre may see an event twice across a switchover but does not miss one.

This is why IEC 104 has no connection pool. A connection is a session: sequence numbers, acknowledgements and command procedures belong to it, and more connections add availability, not throughput.

Plain IEC 104 has no authentication and no encryption. Anyone who can reach port 2404 can interrogate a station and send it commands, and anyone on the path can read or alter the traffic. Keep plain IEC 104 on isolated networks and never expose it to the Internet.

Two standards add security:

IEC 62351-3 (TLS) IEC 62351-5 (application layer)
What it protects The TCP connection: encryption, server and client certificates Individual ASDUs: challenge and reply, session and update keys, message authentication codes
Default port 19998 Runs inside the IEC 104 connection; IEC TS 60870-5-7 says how it applies to IEC 60870-5-101 and -104
OT Fabric support Yes, client and server, with mutual authentication No. The type identifications and causes are named and carried as raw payload; the procedures are not implemented

TLS authenticates the connection, not the individual command. With TLS and client certificates the station knows which control centre is connected, and authorizes commands by that certificate. The OT Fabric projects document why IEC 62351-5 is not implemented yet: the 2023 edition with IEC TS 60870-5-7:2025 differs from the 2013 one, and none of the three open-source stacks they test against has an implementation to verify against.

IEC 104 is the telecontrol protocol of power system SCADA:

  • links between grid control centres and substations, in transmission and distribution networks;
  • RTUs and substation gateways, often in front of IEC 60870-5-101 serial devices;
  • solar parks, wind farms and battery storage that report to and take set points from a grid operator.

Source code: go-iec104, iec104ctl, iec104-interop. Read on in the Go library, iec104ctl and testing and interop pages.