CLI toolsiec103ctl
Poll IEC 103 protection relays: general interrogation, general commands, clock, identification, settings through the generic services, recorded faults with their disturbance data as JSON or CSV, monitoring and line scans, or simulate a relay. Part of iec60870ctl.
Install
Linux and macOS
curl -fsSL https://get.otfabric.io/iec103ctl | sh
Windows (PowerShell)
irm https://get.otfabric.io/iec103ctl.ps1 | iex
CI, containers and device images
curl -fsSL https://get.otfabric.io/iec103ctl | env OTF_UNMANAGED_INSTALL=/usr/local/bin sh
One static binary for Linux (x86-64, ARM64, ARMv7), macOS (Intel, Apple silicon) and Windows (x86-64, ARM64), with no runtime to install. The installer checks the release's SHA-256 checksum, installs per user without sudo, and upgrades in place when you run it again. Pin a release withOTF_VERSION. All install options. To build from source: go install github.com/otfabric/iec60870ctl/cmd/iec103ctl@latest.
First commands
# No relay at hand: start the built-in demo device
iec103ctl server start
# Who is it?
iec103ctl client identify --url tcp://127.0.0.1:2401
# The state of every indication: general interrogation
iec103ctl client interrogate --url tcp://127.0.0.1:2401
# Settings of group 1, through the generic services
iec103ctl client generic group --url tcp://127.0.0.1:2401 --group 1 --format table
# Recorded faults, and one fault's disturbance data as CSV
iec103ctl client disturbance list --url tcp://127.0.0.1:2401
iec103ctl client disturbance get --url tcp://127.0.0.1:2401 --fan 1 --csv fault1.csv
The iec103ctl guide walks through every command group, connection option and safety rule.
For scripts, CI and containers
iec103ctl is as easy to read for a pipeline as for a person. It follows the same conventions as every OT Fabric tool, so a script written for one protocol carries over to the next.
- JSON output.
--format json, or IEC103CTL_FORMAT=json for a whole job. One JSON document per command, JSON Lines for streams, and a single {"error": {"kind", "code", "message"}} object on failure. Field names are a documented contract: json-output.md. - Clean streams. The result goes to stdout; progress, connection state and debug traces go to stderr.
- Stable exit codes from the shared OT Fabric table, so a script can tell a missing connection (4) from a timeout (5) or a refusal by the device (6). Which command returns what: exitcodes.md.
- Aligned version reporting.
iec103ctl version --json prints name, version,tag, commit, built, libraries (the OT Fabric stacks inside the binary), go andplatform, with the same keys in every tool. - Pinned installs with
OTF_VERSION, and OTF_UNMANAGED_INSTALL for images that must not touch PATH or shell profiles.
The exit-code table
| Code | Meaning |
|---|
0 | Success |
1 | Findings: the command completed and its result reports problems, such as a file that does not validate or a diagnosis with a failing check |
2 | Usage: unknown command or flag, a missing argument |
3 | Invalid input: a flag value, a file or a combination that does not make sense. Nothing was sent |
4 | Transport: the connection could not be made, or was lost |
5 | Timeout: the device did not answer in time |
6 | Protocol: the device refused the request, or broke the protocol |
7 | Partial success: a valid result was written, and it holds failures |
8 | Unsupported: the device, or this platform, does not support what was asked |
9 | Permission: the device or the operating system refused, such as raw-socket access without the capability |
10 | Output or internal error |
130 | Interrupted by Ctrl-C or SIGTERM before a result |
Each tool uses the codes that apply to it; a code never changes meaning between tools.
In a Dockerfile
FROM debian:bookworm-slim
RUN apt-get update \
&& apt-get install -y --no-install-recommends ca-certificates curl \
&& curl -fsSL https://get.otfabric.io/iec103ctl \
| env OTF_UNMANAGED_INSTALL=/usr/local/bin sh \
&& rm -rf /var/lib/apt/lists/*
ENTRYPOINT ["iec103ctl"]
Scripts, CI and containers has GitHub Actions and GitLab CI examples and shows how to use a simulator as a test fixture.
Protocols
- IEC 60870-5-103: The informative interface of protection equipment: how a substation controller polls protection relays for their state, events, settings and fault records.