Modbus Application Protocol V1.1b3

Modbus

The most widely deployed protocol in industrial automation: meters, inverters, batteries, drives and PLCs.

Transports
TCP, RTU, ASCII, TLS, UDP
Default port
502 (TCP), 802 (TLS)
Library
go-modbus
CLI
modbusctl

Modbus is the most widely deployed protocol in industrial automation. It dates from 1979, it is simple, and almost every energy meter, solar inverter, battery system, drive and PLC speaks it. A client (master) reads and writes four data tables on a server (slave): coils and discrete inputs (bits), and input registers and holding registers (16-bit words).

Where you meet it

  • Energy meters, solar inverters and battery systems, often with a SunSpec register map on top
  • PLCs, drives and remote I/O on the plant floor
  • RS-485 field buses (Modbus RTU) and serial-to-Ethernet gateways

Quickstart

From the command line

Download modbusctl from GitHub Releases, then:

Terminal window
# What is this device? (FC43 Device Identification + FC17 Report Server ID)
modbusctl client identify --ip 192.168.1.10 --server-id
# Which register blocks are readable? (adaptive scan, saved to MCAP)
modbusctl client scan --ip 192.168.1.10 --algo smart --start 0 --end 5000 --output scan.mcap
# Poll four holding registers every second until Ctrl-C
modbusctl client poll --ip 192.168.1.10 --start 100 --count 4
# Serve the scan results as a simulated device on port 1502
modbusctl server static --input scan.mcap --port 1502

Addresses are raw Modbus PDU addresses (0–65535), not “4xxxx” register labels.

From Go

Terminal window
go get github.com/otfabric/go-modbus

Read four holding registers from unit 1 over Modbus TCP:

main.go
package main
import (
"context"
"fmt"
"log"
"time"
"github.com/otfabric/go-modbus"
)
func main() {
client, err := modbus.NewClient(modbus.NewConfig(
modbus.TransportConfig{URL: "tcp://192.168.1.10:502", DialTimeout: 5 * time.Second},
modbus.ExecutionConfig{Timeout: 3 * time.Second},
modbus.ObservabilityConfig{},
))
if err != nil {
log.Fatal(err)
}
if err := client.Open(); err != nil {
log.Fatal(err)
}
defer client.Close()
ctx, cancel := context.WithTimeout(context.Background(), 3*time.Second)
defer cancel()
regs, err := client.ReadRegisters(ctx, 1, 100, 4, modbus.HoldingRegister)
if err != nil {
log.Fatal(err)
}
fmt.Println(regs)
}

What go-modbus supports

Transports Modbus TCP, RTU and ASCII (RS-232/RS-485), TLS (MBAPS), UDP, RTU-over-TCP, RTU-over-UDP, ASCII-over-TCP
Roles Client and server
Function codes Coils, discrete inputs, input and holding registers, mask write, read/write multiple, FIFO, file records, diagnostics, device identification (FC43/14)
Typed values uint16–uint64, float32/64, strings, BCD, IP addresses, timestamps, with explicit byte and word order
SunSpec Marker detection and model-chain discovery; full point decoding in go-sunspec
Go version 1.23 or later

Interoperability

modbus-interop runs go-modbus against libmodbus (C), PyModbus (Python), digitalpetri/modbus (Java), NModbus (C#) and tokio-modbus (Rust), as both client and server.

OT Fabric projects for Modbus

go-modbus

Modbus client and server: TCP, RTU, ASCII, TLS and UDP, typed register codecs, pooling and retries.

go get github.com/otfabric/go-modbus

go-sunspec

SunSpec over Modbus: discovers 112 built-in models and decodes typed, scaled values. Includes the sunspecctl CLI.

go get github.com/otfabric/go-sunspec

modbus-simulator

Deterministic, stateful Modbus TCP device simulator driven by JSON fixtures, for integration tests.

modbusctl

Identify, fingerprint, scan, poll, decode and write Modbus devices. Record to MCAP and replay as a simulator.

go-serial

Cross-platform serial ports for RS-232 and RS-485, with a Modbus RTU preset.

go get github.com/otfabric/go-serial

modbus-interop

Modbus TCP reference stacks: libmodbus, PyModbus, digitalpetri, NModbus and tokio-modbus.