IEC 60870-5-104

IEC 60870-5-104

Telecontrol between grid control centres, substations and generation or storage assets.

Transport
TCP, optional TLS
Default port
2404
Library
go-iec104
CLI
iec104ctl

IEC 60870-5-104 (IEC 104) is the TCP/IP telecontrol protocol of power system SCADA. A controlling station (the control centre) talks to controlled stations (substations, RTUs, generation and storage assets) on TCP port 2404. Each station has a common address, and each data point an information object address. The control centre runs interrogations, receives spontaneous events, and sends commands, often with select-before-operate.

Where you meet it

  • Links between grid control centres and substations
  • Solar parks, wind farms and battery storage connected to a grid operator
  • RTUs and gateways in distribution and transmission networks

Quickstart

From the command line

Download iec104ctl from GitHub Releases. No station at hand? Start a simulated one:

Terminal window
iec104ctl server start

and talk to it from another terminal:

Terminal window
# What does this station hold? (general interrogation)
iec104ctl client interrogate --ip 127.0.0.1 --ca 1
# Watch events and measured values as they arrive, until Ctrl-C
iec104ctl client monitor --ip 127.0.0.1 --interrogate
# Operate a disconnector with select-before-operate
iec104ctl client command --ip 127.0.0.1 --type double --ioa 5001 --value off --mode sbo
# Is the link alive, and how fast?
iec104ctl client ping --ip 127.0.0.1

From Go

Terminal window
go get github.com/otfabric/go-iec104

Connect, interrogate and synchronize the clock:

main.go
package main
import (
"context"
"fmt"
"log"
"time"
"github.com/otfabric/go-iec104/asdu"
"github.com/otfabric/go-iec104/client"
)
func main() {
ctx := context.Background()
// Dial connects and sends STARTDT. Every ASDU the station sends
// reaches the handler, in order.
c, err := client.Dial(ctx, "10.0.0.5:2404",
client.WithReconnect(client.Reconnect{}),
client.WithHandler(client.HandlerFunc(func(a *asdu.ASDU) {
for _, obj := range a.Objects {
if m, ok := obj.(asdu.MeasuredFloat); ok {
fmt.Printf("%s ioa=%d value=%g quality=%s\n", a.Cause, m.IOA, m.Value, m.Quality)
}
}
})))
if err != nil {
log.Fatal(err)
}
defer c.Close()
// General interrogation of station 1.
data, err := c.Interrogate(ctx, 1, asdu.QOIStation)
if err != nil {
log.Fatal(err)
}
fmt.Printf("interrogation returned %d ASDUs\n", len(data))
if err := c.ClockSync(ctx, 1, time.Now()); err != nil {
log.Fatal(err)
}
}

What go-iec104 supports

Roles Controlling station (client) and controlled station (server)
Client STARTDT/STOPDT, general and counter interrogation, read, clock sync, commands with select-before-operate, test command, automatic reconnect
Server Many sessions, routing by type identification, redundancy groups with an acknowledged event queue
Link layer Full APCI state machine: I/S/U frames, k/w windows, t0–t3 timers
Security TLS (IEC 62351-3). IEC 62351-5 application-layer security is not implemented.
Dependencies Go standard library only

Interoperability

iec104-interop tests go-iec104 against MZ Automation lib60870-C, OpenMUC j60870 and wendy512/iec104, as both client and server. It has not been tested against certified test equipment.

OT Fabric projects for IEC 60870-5-104

go-iec104

IEC 60870-5-104 controlling and controlled station, with the full APCI state machine and redundancy groups.

go get github.com/otfabric/go-iec104

iec104ctl

Interrogate, monitor and command IEC 104 stations, transfer files, or simulate an RTU from YAML.

iec104-interop

IEC 104 reference stations: lib60870, OpenMUC j60870 and wendy512.