IEC 61850-7-2, 7-3, 7-4 and 7-4xx · NSD per IEC 61850-7-7

IEC 61850 information model

The standard semantics of IEC 61850: logical node classes, data objects, common data classes, data attributes and functional constraints, read from the official NSD files and usable without any transport.

Category
Information model
Machine-readable form
NSD (IEC 61850-7-7)
Standards organization
IEC TC 57
Library
go-iec61850-model
CLI
nsdctl
Communication
go-iec61850, go-mms

The IEC 61850 information model is the part of IEC 61850 that says what the data in a power system device means, independent of how it travels. It is not a communication protocol. A breaker position, a three-phase voltage or a battery’s state of charge has the same name, type and structure whether a client reads it over MMS, a device publishes it in GOOSE, or an engineering tool only looks it up.

What the model defines

Concept What it is Example
Logical node class A function of a device, named by four letters; the first letter is its group MMXU measurement unit, XCBR circuit breaker, DBAT battery
Data object A named piece of information inside a logical node, with a presence condition (mandatory, optional, conditional) MMXU.Hz frequency, XCBR.Pos position
Common data class (CDC) The structure of a data object: which attributes it has MV measured value, WYE three-phase values, DPC controllable double point
Data attribute A typed leaf or structure inside a CDC mag.f (FLOAT32), q (Quality), t (Timestamp), stVal
Functional constraint (FC) What an attribute is for, and which services may use it MX measurands, ST status, CO control, CF configuration, SP settings
Enumerations and basic types The allowed values and primitive types SIUnit, BehaviourModeKind, INT32, FLOAT32

IEC 61850-7-3 defines the common data classes, IEC 61850-7-4 the core logical nodes, and domain parts such as IEC 61850-7-420 (DER, inverters, storage) and 7-410 (hydropower) add their own. IEC 61850-7-2 defines the abstract services (ACSI) that act on this model.

A device reference ties the levels together: in LD0/MMXU1.PhV.phsA.cVal.mag.f[MX], LD0 is a logical device on the IED, MMXU1 an instance of the MMXU class, PhV a data object of CDC WYE, and phsA.cVal.mag.f the path down to a FLOAT32, read with functional constraint MX.

NSD: the model in machine-readable form

IEC 61850-7-7 defines NSD (namespace definition) files, the XML form in which IEC publishes each namespace: its classes, data objects, CDCs, types, enumerations and the dependencies between namespaces. NSD files are versioned per namespace release (for example IEC 61850-7-4:2007B6), so two editions of a part can be loaded and compared side by side.

Normative model, device instance and interpretation

Three things are easy to confuse, and go-iec61850-model keeps them apart:

  1. Normative model. What a namespace release defines: MMXU has an optional data object Hz of CDC MV. This is what the NSD files say, and what go-iec61850-model implements.
  2. Device instance. What one IED actually implements: LD0/MMXU1.Hz exists on this device. That comes from its SCL file or from browsing it over MMS with go-iec61850. A reference that resolves against the model is valid, but it does not prove a device has it.
  3. Semantic inference. What a value means in engineering terms, such as “line-to-ground voltage, phase A, expected in volts”. go-iec61850-model derives this from explicit, documented rules, marks it as OT Fabric’s interpretation with the rule and confidence, and never changes the normative model with it. Application-specific mappings, for example into a historian’s tag names, belong in this layer too.

Quickstart

From the command line

nsdctl is included with go-iec61850-model. Download it from GitHub Releases or go install github.com/otfabric/go-iec61850-model/cmd/nsdctl@latest. The official catalog is embedded, so it needs no files:

Terminal window
# What does a logical node hold, inherited data objects included?
nsdctl model show MMXU
# What does this reference mean, and what type is it?
nsdctl model describe 'LD0/MMXU1.PhV.phsA.cVal.mag.f[MX]'
nsdctl model show 'LD0/MMXU1.PhV.phsA.cVal.mag.f[MX]'
# Which attributes does a client read for total active power?
nsdctl model leaves MMXU.TotW --fc MX
# The same name in two namespaces: compare instead of merging
nsdctl catalog overlaps --left IEC_61850-7-420 --right IEC_TR_61850-90-9

From Go

Terminal window
go get github.com/otfabric/go-iec61850-model

Look up a class and resolve a reference down to its basic type with the embedded catalog (from the go-iec61850-model README):

main.go
p, err := official.Default() // IEC 61850-7-2, 7-3, 7-4, 7-410 and 7-420
if err != nil {
log.Fatal(err)
}
dos, _ := p.DataObjects("MMXU") // what MMXU holds, inherited data objects included
res, _ := resolver.New(p).ResolveString("LD0/MMXU1.Hz.mag.f[MX]")
fmt.Println(len(dos), res.Type()) // FLOAT32
d, _ := semantic.Describe(p, "MMXU.PNV.phsA.cVal.mag.f")
fmt.Println(d.Quantity, d.Phase, d.Reference, d.UnitHint) // voltage A line-neutral V

What go-iec61850-model supports

The library is pre-release (v0.1.x). Its own status table is the reference; this is a summary.

NSD importer Reads NSD and NSDoc XML and ZIP packages, treated as untrusted input; tested against the 14 tracked official packages with no validation errors
Embedded catalog The 12 official NSD namespaces (7-2, 7-3, 7-4, 7-410, 7-420 and the technical reports 90-3, 90-4, 90-6, 90-9, 90-11, 90-14, 90-21), with a default and an extended profile
Editions Several releases of a namespace in one catalog, explicit profiles, never a silent “latest”; names defined by two namespaces fail as ambiguous until you choose
References Parsing compatible with go-iec61850’s ParseRef, and validation against the model
Type resolution Paths down to basic types, with inheritance, parameterized CDCs, multi-instance data objects and FC checks
Semantic mapping Quantity, phase, reference, component and unit hints from explicit rules for MMXU, MMXN and MMTR, with overrides
Ontology helpers A typed concept graph with traversal and JSON export
Generated code Typed Go constants for every class, data object, CDC and enumeration of the default profile
Coverage 93% of the concrete data objects resolve to leaf types; the rest hit gaps in the published packages
Not covered MMS, GOOSE, Sampled Values and any other communication; an SCL runtime; the service namespace of IEC 61850-8-1, which is recognized but not modeled; an NSD update monitor (planned)
Go version 1.24 or later, standard library only (nsdctl adds cobra)

Communication is a separate layer

Using the information model does not mean speaking every IEC 61850 communication mapping. The model is defined once; IEC 61850-8-1 maps it onto MMS for client/server communication and onto GOOSE for fast peer-to-peer events, and IEC 61850-9-2 onto Sampled Values. OT Fabric’s projects split along the same line:

Project Layer What it does
go-iec61850-model Information model The normative catalog from NSD: lookups, validation, resolution, semantics. No transport.
go-iec61850 Communication, MMS mapping IEC 61850 client and SCL-driven server over MMS: browse, read, write, datasets, reports, controls, files. No GOOSE or Sampled Values.
go-mms Protocol MMS (ISO 9506) client and server, the transport underneath go-iec61850.

go-iec61850-model imports neither go-iec61850 nor go-mms, and go-iec61850 does not depend on it today. See IEC 61850 / MMS for the communication side.

Standards and licensing

The IEC 61850 parts are published by the IEC through TC 57, and the official NSD packages are IEC code components under the IEC Code Components licence. go-iec61850-model is MIT-licensed. It ships no NSD files and no text from the standards: its embedded catalog, generated constants and model reference hold identifiers, types and structure derived from the official packages, published under the IEC Code Components licence with IEC attribution. Nothing in the repository grants rights to the standards themselves; you still need them to implement IEC 61850 correctly.

OT Fabric projects for IEC 61850 information model

go-iec61850-model

The IEC 61850 information model without a transport: an edition-aware catalog of logical nodes, data objects, CDCs and data attributes from the official NSD files, with reference validation, type resolution and semantic mapping.

go get github.com/otfabric/go-iec61850-model
  • IEC 61850 model
GitHub

nsdctl

The CLI included with go-iec61850-model: look up what an IEC 61850 logical node holds, explain a reference, and inspect, validate, compare and generate from NSD packages.

Who is behind IEC 61850 information model

The organizations that publish, test, certify or host open-source work for IEC 61850 information model. Listed for reference, not as partners. Compare membership and fees.