S7 communication over ISO-on-TCP (RFC 1006)

Siemens S7

Classic S7 communication with Siemens PLCs, for reading and writing data blocks, inputs, outputs and markers.

Transport
S7 over COTP and TPKT
Default port
102
Library
go-s7comm
CLI
s7commctl

S7 communication is the protocol Siemens PLCs speak on port 102. It runs on a stack of ISO transports: TPKT framing (RFC 1006), then COTP (ISO 8073, class 0), then the S7 PDUs themselves. A client connects to a CPU by rack and slot, then reads and writes memory areas: data blocks (DB), inputs (I), outputs (Q) and markers (M). OT Fabric builds this stack from go-tpkt, go-cotp and go-s7comm.

Where you meet it

  • Siemens PLCs on factory floors and in process plants
  • Utility and building systems controlled by Siemens CPUs
  • Legacy integrations where OPC UA is not enabled on the PLC

Quickstart

From the command line

Terminal window
# Find S7 devices on a subnet
s7commctl discover --cidr 192.168.1.0/24 --format json
# Which rack/slot combinations does a target accept?
s7commctl probe rackslot --ip 192.168.1.10 --format table
# What is it? (SZL-based identification)
s7commctl identify --ip 192.168.1.10 --rack 0 --slot 1 --format json
# Read 16 bytes from DB1
s7commctl read --ip 192.168.1.10 --area DB --db 1 --offset 0 --size 16 --format hex

Reads are safe by default. Writes need --dangerous, and ask for confirmation unless you pass --force.

From Go

Terminal window
go get github.com/otfabric/go-s7comm

Read 16 bytes from DB1:

main.go
package main
import (
"context"
"fmt"
"log"
"time"
"github.com/otfabric/go-s7comm/client"
)
func main() {
ctx, cancel := context.WithTimeout(context.Background(), 5*time.Second)
defer cancel()
c := client.New("192.168.0.10", client.WithRackSlot(0, 1))
if err := c.Connect(ctx); err != nil {
log.Fatal(err)
}
defer func() { _ = c.Close() }()
result, err := c.ReadDB(ctx, 1, 0, 16)
if err != nil {
log.Fatal(err)
}
if err := result.Err(); err != nil {
log.Fatal(err)
}
fmt.Printf("DB1.DBB0..15 = % X\n", result.Data)
}

What go-s7comm supports

Role Client
Areas Read and write DB, inputs, outputs and markers, plus native single-bit reads and writes
Discovery CIDR scans with rack/slot probing, readable-range scans
Diagnostics SZL-based identification, block listing, block metadata and upload
Go version 1.23 or later

Interoperability

snap7-interop runs two independent Snap7 servers (native and pure Python) from the same compiled fixtures, covering data blocks, markers, inputs and outputs, typed values and bit access.

OT Fabric projects for Siemens S7

go-s7comm

Siemens S7 client: read and write DBs, inputs, outputs and markers, discovery and SZL diagnostics.

go get github.com/otfabric/go-s7comm

s7commctl

Siemens S7 command-line client for ISO-on-TCP (port 102).

go-cotp

COTP TP0 transport service over RFC 1006, plus a full X.224 TPDU codec.

go get github.com/otfabric/go-cotp
  • Siemens S7
  • IEC 61850 / MMS
GitHub

go-tpkt

TPKT framing for RFC 1006 and RFC 2126 transport profiles.

go get github.com/otfabric/go-tpkt
  • Siemens S7
  • IEC 61850 / MMS
GitHub

snap7-interop

Fixture-driven Snap7 servers (native and pure Python) for testing S7 clients.