Go library

go-profinet implements PROFINET IO in Go, in both roles: an IO-Controller (package controller) and an IO-Device (package device), on its own DCP, LLDP, connectionless DCE/RPC, PNIO block codecs, RT cyclic layer and alarm transport. It has no dependencies outside the Go standard library and no cgo. The authoritative reference for each symbol is the godoc on pkg.go.dev; API.md in the repository is the map. This page follows v0.6.0.

Terminal window
go get github.com/otfabric/go-profinet

Go 1.23 or later. The main packages:

Package Contents
controller IO-Controller, record client, device access (supervisor) ARs
device IO-Device
model The device model: identity, DAP, slots, modules, submodules, records
dcp, lldp DCP requester and responder; LLDP codec, agent and neighbor table
rpc, pnio Connectionless DCE/RPC; PNIO blocks, NDR, status codes
rt, alarm Cyclic frames, layout, provider, consumer and scheduler; the RTA alarm transport
gsdml, gsdml/gsdx GSDML documents, validation and model conversion; an inspector of GSDX containers
mrp, snmp, l2/bridge Media redundancy, a read-only SNMP agent, the software switch of a multiport device
l2/osport, vnet, netstack Raw Ethernet of the platform, a virtual Ethernet with seeded faults, a small ARP/IPv4/UDP stack

PROFINET runs partly on raw Ethernet, so the first step is a port and a frame demultiplexer. osport picks AF_PACKET on Linux, BPF on macOS and the BSDs, and Npcap on Windows:

port, err := osport.Open("eth0", osport.Options{})
if err != nil {
return err // needs CAP_NET_RAW, /dev/bpf* or Npcap
}
defer port.Close()
mux := l2.NewMux(port)
defer mux.Close()

Records and the Connect use the operating system’s UDP stack on port 34964, unless you give a component a ListenPacket of its own.

ctrl, err := controller.New(controller.Config{
Mux: mux,
StationName: "plc-1", // CMInitiatorStationName
VendorID: 0xF000, DeviceID: 1, Instance: 1, // the controller's object UUID
})
defer ctrl.Close() // releases every AR
d, err := ctrl.AddDevice(controller.DeviceConfig{
StationName: "io-rack-1",
Model: m, // from gsdml.ToModel or written by hand
IP: suite, AssignIP: true, // set the address with DCP if it differs
ReductionRatio: 4, // 4 ms with the 1 ms send clock
Parameters: []controller.Parameter{{Slot: 2, Subslot: 1, Index: 0x10, Data: []byte{0, 2}}},
OnState: func(from, to controller.State, err error) { log.Printf("%s → %s %v", from, to, err) },
OnAlarm: func(a controller.AlarmEvent) { log.Printf("alarm %s slot %d", a.Notification.Type, a.Notification.Slot) },
})
err = d.WaitState(ctx, controller.StateRunning)

Each device runs its lifecycle on its own goroutine: Resolving (DCP Identify by name, optionally Set IP), Connecting, Parameterizing (the Parameters, then PrmEnd), WaitApplicationReady and Running. A failure in any state goes back to Offline and retries with exponential backoff (200 ms doubling to 10 s, with optional jitter). A DCP Hello from the device skips the wait. Advanced: true uses the advanced startup with RT_CLASS_2, which pnio-rs needs; otherwise the controller uses the legacy startup with RT_CLASS_1.

While it runs:

d.SetOutput(2, 1, out, pnio.IOxSGood)
in, iops, ok := d.Input(1, 1)
b, err := d.ReadRecord(ctx, controller.Record{Slot: 1, Subslot: 1, Index: 0x10}, 0)
err = d.WriteRecord(ctx, controller.Record{Slot: 2, Subslot: 1, Index: 0x10}, []byte{0, 3})
im0, err := d.ReadIM0(ctx)
diags, err := d.ReadDiagnosis(ctx)
diff := d.ModuleDiff() // what the device reported as different
st := d.Stats() // connects, aborts, alarms, provider, consumer, cycle jitter

Alarms are acknowledged before OnAlarm runs. A device whose real configuration differs still runs: the ModuleDiffBlock says which submodules are wrong, and their IO data carries IOPS bad.

A record client reads records with ReadImplicit, and a device access AR (IOSAR) writes them without IO data:

rc := controller.NewRecordClient(ctrl.RPC(), &net.UDPAddr{IP: ip, Port: rpc.Port}, pnio.ObjectUUID(inst, devID, vendorID))
im0, err := rc.ReadIM0(ctx, rpc.NilUUID, 0, 1)
sar, err := rc.OpenSupervisor(ctx, controller.SupervisorConfig{InitiatorMAC: mux.HardwareAddr(), InitiatorObject: ctrl.ObjectUUID()})
err = sar.Write(ctx, controller.Record{Slot: 2, Subslot: 1, Index: 0x10}, data)
err = sar.Release(ctx)

Devices that do not accept device access ARs, such as p-net, refuse it; write in an IOCAR instead.

Shared devices, re-parameterization and port checks

Section titled “Shared devices, re-parameterization and port checks”

Several controllers can share a device: give each a model with only its slots (m.WithSlots(1, 3)). A submodule another controller owns comes back in the ModuleDiff as locked. When its owner leaves, the device hands it over with a Released alarm, and the controller parameterizes it and takes over its data. d.Reparameterize(ctx, params) re-parameterizes a running AR (PrmBegin, writes, PrmEnd, ApplicationReady) while cyclic data goes on. DeviceConfig.PeerChecks writes the expected neighbour of a port, and DeviceConfig.MRP the MRP role of a multiport device.

Describe the device with a model. The same model generates its GSDML file and is what a go-profinet controller expects:

m := &model.Device{
Identity: model.Identity{VendorID: 0xF000, DeviceID: 0x0001, VendorName: "ACME", TypeOfStation: "ACME IO",
OrderID: "ACME-IO-1", SerialNumber: "0001", HardwareRevision: 1,
SoftwareRevision: pnio.SoftwareRevision{Prefix: 'V', FunctionalEnhance: 1}},
Capabilities: model.Capabilities{MaxARs: 2, MinDeviceInterval: 32, ConformanceClass: "B", Ports: 1, LLDP: true},
DAP: model.StandardDAP("ACME DAP", 0x00000100, 1), // identity, interface and one port
Slots: []model.Slot{
{Number: 1, Module: model.Module{Name: "8 in", IdentNumber: 0x10,
Submodules: []model.Submodule{{Name: "Inputs", IdentNumber: 0x11, Subslot: 1, InputLen: 8}}}},
{Number: 2, Module: model.Module{Name: "4 out", IdentNumber: 0x20,
Submodules: []model.Submodule{{Name: "Outputs", IdentNumber: 0x21, Subslot: 1, OutputLen: 4,
Records: []model.Record{{Index: 0x10, Name: "Mode", Length: 2, Default: []byte{0, 1}}}}}}},
},
}
dev, err := device.New(device.Config{
Model: m, Mux: mux, StationName: "acme-io-1", IP: suite,
ApplyIP: func(s dcp.IPSuite, permanent bool) error { return configureOS(s) },
Handler: &app{}, // embed device.NopHandler
})
defer dev.Close()
dev.SetInput(1, 1, data, pnio.IOxSGood) // every AR's next frames carry it
out, iops, ok := dev.Output(2, 1) // what the controller last sent

go-profinet never changes the operating system’s addresses: a DCP Set IP reaches ApplyIP, which must configure the interface. The Handler decides what the application handles itself: records without a model entry, the end of parameterization (return nil when the application is ready, and the device sends ApplicationReady), AR state changes and DCP Signal, reset, name and IP events.

err := dev.SendAlarm(ctx, device.Alarm{Type: pnio.AlarmProcess, Slot: 1, Subslot: 1, HasItem: true, USI: 0x10, Data: []byte{1}})
err = dev.AddDiagnosis(ctx, 1, 1, pnio.DiagnosisItem{ChannelNumber: 1, ErrorType: pnio.ChannelErrLineBreak})

More options on device.Config:

  • Persistence. Store (package store) keeps the station name and IP suite of a permanent DCP Set and every I&M1 to I&M4 write across restarts; a temporary Set is lost on restart, as on p-net.
  • DCP Hello. Hello: dcp.HelloOnLinkUp announces the device at start and on link up while no controller is connected.
  • Multiport devices and MRP. Bridge runs the ports on a software switch, and MRP makes two of them a ring port pair as client, manager or automatic manager, with the 200 ms or 500 ms profile.
  • SNMP. SNMP starts a read-only v1/v2c agent with MIB-II and the LLDP-MIB of the ports.
  • DCP policy. DCPPolicy can make the device read-only for DCP Set and reset, rate-limit requests and audit every Set. It is not a security class: MAC addresses can be forged.
c, err := dcp.NewClient(mux, dcp.ClientOptions{}) // or ctrl.DCP()
devices, err := c.Identify(ctx, dcp.FilterAll(), dcp.IdentifyOptions{Wait: 2 * time.Second, ResponseDelay: 10})
id, err := c.IdentifyName(ctx, "io-rack-1", time.Second) // profinet.ErrNotFound when none answers
err = c.SetName(ctx, mac, "io-rack-1", true) // permanent
err = c.SetIP(ctx, mac, dcp.IPSuite{Addr: ip, Mask: mask, Gateway: gw}, false)
err = c.Signal(ctx, mac)

Station names are validated before anything is sent. Get and Set are retransmitted, because devices ignore other requesters for 3 seconds after a Get or Set.

doc, err := gsdml.Parse(f) // UTF-8 or ISO-8859-1
err = gsdml.Validate(doc) // *gsdml.ValidationError lists each issue
m, err := gsdml.ToModel(doc, "") // the first device access point
out, err := gsdml.FromModel(m, gsdml.GenerateOptions{SupervisorAR: true})
b, err := gsdml.Marshal(out)
name := gsdml.FileName(m, "", time.Now()) // GSDML-V2.35-<vendor>-<family>-<date>.xml

ToModel turns one device access point into a model: identity, capabilities, the modules fixed or used in slots and the rest as a catalog to plug from, with IO data lengths and parameter records with defaults. Validation follows an independent catalog of the schema for versions 2.25 to 2.45, because the official schemas are licensed to PI members; a file it accepts may still fail PI’s checker.

vnet is an in-memory switch with seeded loss, duplication, corruption, reordering, delay and jitter, and netstack a small ARP, IPv4 and UDP stack on top. A controller and any number of devices run in one process, with no privileges, which is how the quickstart and the end-to-end and chaos tests work.

Every error matches one of the sentinels of the root package with errors.Is: ErrTimeout, ErrRejected, ErrNotFound, ErrUnsupported, ErrInvalidState, ErrAborted, ErrMalformed, ErrResourceExhausted, ErrLinkDown, ErrInvalidConfig and ErrClosed. Typed errors keep the protocol’s codes: *pnio.StatusError carries the PNIO status, *dcp.SetError the refused block, *rpc.Fault the RPC status.

_, err := d.ReadRecord(ctx, controller.Record{Slot: 1, Subslot: 1, Index: 0x10}, 0)
var se *pnio.StatusError
switch {
case errors.As(err, &se) && errors.Is(err, profinet.ErrNotFound):
log.Printf("no such record: %s", se.Status) // DE 80 B0 00 (read: access: invalid index)
case errors.Is(err, profinet.ErrTimeout):
log.Print("no answer")
}

Record calls are never retried behind the application’s back, so a write is not repeated by surprise. ERRORS.md lists every code.

Every component takes an optional profinet.Logger, with adapters for log/slog and the standard logger; nothing is logged per frame. controller.Config.Metrics and device.Config.Metrics take a profinet.Metrics with callbacks for state changes, connects, aborts, record accesses with their durations, alarms and retries, and every component keeps counters. See OBSERVABILITY.md.

The examples directory has runnable programs, most of them self-contained on the virtual network: quickstart, discovery, hello, alarms, records, topology, observability, mrp (a ring with a cut cable), chaos, gsdml, gsdmlimport and gsdx; device and controller work on a real interface.

Terminal window
go run ./examples/quickstart
  • Conformance class A features as controller and device, with RT_CLASS_1 and unsynchronized RT_CLASS_2, shared device, multiport devices and MRP (no MRPD, no interconnection). This is feature coverage, not conformance.
  • Not implemented: IRT (RT_CLASS_3) and PTCP time synchronization, PROFIsafe, the PROFINET security classes, shared input, MCR, RT over UDP beyond codecs, SNMP writes, SNMPv3 and traps. System redundancy S2 is an experiment that is off by default and not interoperable.
  • Timing: cyclic data runs on Go timers on a general-purpose OS. A 1 ms cycle holds on Linux and macOS with occasional outliers that the default watchdog of 10 cycles absorbs; it is not for motion control or safety reaction times.
  • Platforms: AF_PACKET is tested in CI and by the interop suite, BPF on macOS in CI as root; Npcap on Windows is cross-compiled but not tested against Npcap.
  • Not certified by PI, and no conformance claim. OT Fabric is not a PI member, so GSDML validation uses an independent catalog and GSDX signatures are not verified. A product needs its own vendor ID; examples use 0xF000.

The complete list is in LIMITATIONS.md, and what PI membership would change in docs/PI-MEMBERSHIP.md.