PROFINET IO: IEC 61158-5-10 and 61158-6-10, IEC 61784-2 (CPF 3); PROFIBUS & PROFINET International

PROFINET

The industrial Ethernet of PLCs, remote I/O, drives and field devices: IO-Controllers find their IO-Devices by name with DCP, set them up over DCE/RPC and exchange their process data in cyclic real-time frames, with alarms, diagnosis and media redundancy.

Transport
Ethernet 0x8892 (DCP, cyclic RT, alarms), DCE/RPC on UDP 34964, LLDP
Roles
IO-Controller, IO-Device and IO-Supervisor
Library
go-profinet
CLI
profinetctl
Interop
profinet-interop v0.6.0

PROFINET IO is the industrial Ethernet that PROFIBUS & PROFINET International (PI) maintains and that Siemens and many other automation vendors build on. An IO-Controller, usually a PLC, owns a set of IO-Devices: remote I/O stations, drives, valve terminals, robots, sensors and gateways. It finds each one by its station name with DCP, establishes an application relationship (AR) with the configuration it expects, writes the parameters, and then exchanges the process data in cyclic real-time frames directly on Ethernet, every few milliseconds, with a status byte next to every value. Alarms, diagnosis and records travel next to the cyclic data, and a GSDML file describes each device to the engineering tool.

Where you meet it

  • Factory and process automation with Siemens SIMATIC controllers and the many PLCs, drives and I/O systems that speak PROFINET, often next to EtherNet/IP and Modbus TCP in the same plant
  • Machine building, packaging, automotive and logistics lines, where commissioning means naming devices, assigning addresses and checking the cabling
  • Ring networks with media redundancy (MRP), so that one broken cable does not stop a line
  • Energy and infrastructure sites run by the same controllers: battery storage, water treatment, tunnels and building plant

Quickstart

From the command line

Download profinetctl from GitHub Releases, or go install github.com/otfabric/profinetctl@latest. DCP and cyclic data are raw Ethernet, so most commands need root or CAP_NET_RAW on Linux, BPF access on macOS or Npcap on Windows:

Terminal window
# Which PROFINET devices are on eth0?
sudo profinetctl -i eth0 discover
# Name a new device (it has no name yet: select it by MAC) and give it an address
sudo profinetctl -i eth0 name set io-rack-1 --mac 00:0e:cf:12:34:56 --permanent
sudo profinetctl -i eth0 ip set 192.168.0.10/24 -s io-rack-1 --permanent
# Flash its LED to find it in the cabinet, then read identification and health
sudo profinetctl -i eth0 signal -s io-rack-1
sudo profinetctl -i eth0 im read -s io-rack-1
sudo profinetctl -i eth0 diagnostics -s io-rack-1
# Which device is plugged into which port?
sudo profinetctl -i eth0 topology
# Connect as IO-Controller with the device's GSDML file and watch its inputs
sudo profinetctl -i eth0 io monitor -s io-rack-1 --gsdml GSDML-V2.35-Vendor-Device-20240101.xml

Output is text, a table or JSON with stable exit codes. Commands that change a device say so, and reset needs --confirm.

From Go

Terminal window
go get github.com/otfabric/go-profinet

An IO-Controller and an IO-Device in one process, on the in-memory virtual Ethernet, so it needs no privileges (abridged from the go-profinet README):

main.go
network := vnet.New(1)
dn, _ := vnetenv.NewNode(network, 10, "192.168.0.10") // an endpoint with an IP stack
dev, _ := device.New(device.Config{
Model: model, Mux: dn.Mux, StationName: "io-1",
IP: suite("192.168.0.10"), ListenPacket: dn.Stack.ListenPacket,
})
cn, _ := vnetenv.NewNode(network, 1, "192.168.0.1")
ctrl, _ := controller.New(controller.Config{Mux: cn.Mux, ListenPacket: cn.Stack.ListenPacket, StationName: "plc-1"})
io1, _ := ctrl.AddDevice(controller.DeviceConfig{StationName: "io-1", Model: model})
_ = io1.WaitState(ctx, controller.StateRunning)
dev.SetInput(1, 1, []byte("PROFINET"), pnio.IOxSGood)
io1.SetOutput(2, 1, []byte{1, 2, 3, 4}, pnio.IOxSGood)
in, iops, _ := io1.Input(1, 1)

On a real network, osport.Open("eth0", ...) opens AF_PACKET, BPF or Npcap, and the expected configuration of a device usually comes from its GSDML file:

doc, err := gsdml.Parse(f)
m, err := gsdml.ToModel(doc, "") // the first device access point
d, err := ctrl.AddDevice(controller.DeviceConfig{StationName: "io-rack-1", Model: m})

What go-profinet and profinetctl support

Roles IO-Controller (one lifecycle per device, reconnects with backoff), IO-Device (several ARs, shared device) and device access ARs for engineering tools
Discovery and addressing DCP Identify with filters, Get, Set of station name and IP suite (temporary or permanent), Signal, ResetToFactory and Hello, as requester and responder
Cyclic data RT_CLASS_1 (legacy startup) and RT_CLASS_2 without synchronization (advanced startup), IOPS and IOCS, watchdogs and data hold
Acyclic Records over connectionless DCE/RPC, ReadImplicit, WriteMultiple, I&M0 to I&M4, diagnosis, ModuleDiff, re-parameterization of a running AR
Alarms Both priorities and all alarm types, with acknowledgement and retransmission
Topology and redundancy LLDP agent and neighbor table, port data and CheckPeers, multiport devices on a software switch, MRP client, manager and automatic manager, a read-only SNMP agent
GSDML Parse, validate against an independent schema catalog, convert to and from device models, generate a device’s own file
Platforms Linux AF_PACKET, macOS and BSD BPF, Windows Npcap, and a virtual Ethernet with seeded faults for tests. No dependencies outside the Go standard library

OT Fabric projects for PROFINET

go-profinet

PROFINET IO-Controller and IO-Device: DCP, LLDP, records, I&M, diagnosis, alarms, cyclic RT data, shared device, MRP rings and GSDML. Raw Ethernet on Linux, macOS and Windows. No dependencies.

go get github.com/otfabric/go-profinet

profinetctl

Discover PROFINET devices, set station names and IP addresses, read I&M, records and diagnosis, map the cabling, check GSDML files, and connect as IO-Controller to watch cyclic IO and alarms.

profinet-interop

Independent PROFINET references in containers: rt-labs p-net and pnio-rs as IO-Devices, profinet-py as IO-Controller, pnio-dcp, two MRP ring nodes, Net-SNMP, and Wireshark and scapy as decoders.

Who is behind PROFINET

The organizations that publish, test, certify or host open-source work for PROFINET. Listed for reference, not as partners. Compare membership and fees.